www.miinet.com
Moore Industries-International, Inc.
- 56 -
User’s Manual
224-790-00K
May 2018
Programmable Limit Alarm Trips
SPA
2
SECTION 4
Duplicate (Copy) Alarm Configuration
Figure 4.19 Gives an overview of the Duplicate (Copy) Alarm configuration menu.
This option is not a new type of alarm. It just provides the facility to make a one time copy of an
alarm configuration.
1. At the “CONFG ALARM” menu, press
SELECT
. Use the
UP
and
DOWN
buttons to toggle
between the alarms. When the desired alarm appears, press
SELECT.
2. At the “ALARM TYPE” menu, press
SELECT.
From here you will choose your alarm type.
Use the
UP
and
DOWN
buttons to scroll through the selections. Press
SELECT
once
“ALARM DULPI” is displayed.
3. At “COPY ALRMX” press
SELECT
and use the
UP
and
DOWN
buttons to set which alarm to
duplicate. Press
SELECT
. You may also
SELECT
“COPY CANCL” to cancel the duplication
process.
4. Once you press
SELECT
on any particular alarm the menu will jump top the first parameter for
that duplicated alarm and allow you to modify the duplicated parameters.
Note:
When using Copy alarm make sure to check that you have updated the settings to the most
current . Also be aware that if changes are made to the original alarm from which a duplicate
was created, all changes will
not
be updated to the duplicate alarm if changes are made after
the duplication.
CONFG
ALARM
D
D
D
D
U
U
U
U
CONFG
ALARM1
CONFG
ALARM2
CONFG
ALARM3
CONFG
ALARM4
ALARM
EXIT
SEL
D
U
If more alar
ms are to be programmed
If
AL2
If
AL3
If
AL4
SEL
SEL
SEL
ALARM
TYPE
COPY
ALARM X*
or
CANCEL
DEPENDING
on ALARM X*
SELECTED
MENU WILL
LEAD TO FIRST
PARAMETER OF
COPIED ALARM
D
U
SEL
PASSWORD menu
Proceed to ALARM EXIT if
no more alarms are to be programmed
*The alar
m channel being programmed
ALARM
TRIP
FAULT
ROC
BAND
STUCK
DUPLI
U/D
D
U
SEL
SEL
IF COPY ALARM X*
IF CANCEL
SEL
If DUPLI
U/D
Figure 4.19.
CONFG ALARM Menu (DUPLI Alarm, Copy Alarm)