38
Electrical installation
Room sensor BT50
Refer to Room sensor BT50 for RC-HY20 for function and
installation place.
&RQQHFWWKHURRPVHQVRUWRWHUPLQDOEORFN;DQG;RQ
the input board (AA3).
If the sensor is to be used to change the room temperature in
°C and/or to change/stabilise the room temperature, the sensor
must be activated in menu 1.9.4.
,IWKHURRPVHQVRULVXVHGLQDURRPZLWKXQGHUÀRRUKHDWLQJLW
should only have an indicatory function, not control of the
room temperature.
SMO Externt
2
3
4
5
6
7
8
9
AA3-X6
External
RC-HY40
BT50
AA3-X6
RC-HY40
CAUTION
Changes of temperature in accommodation
take time. For example, short time periods in
combination with underfloor heating will not
give a noticeable difference in room temperature.
t 4UFQDPOUSPMMFEBEEJUJPOBMIFBU
Refer to the explanation for RC-HY20.
t 3FMBZPVUQVUGPSFNFSHFODZNPEF
Refer to the explanation for RC-HY20.
t &YUFSOBMDJSDVMBUJPOQVNQ
Refer to the explanation for RC-HY20.
RC-HY40
Load monitor
In case many power electrical appliances are connected in the
property and the electric heater is energised at the same time,
there is a risk of tripping the main fuse of the property.
The control module has an integrated load monitor that controls
the power steps of the electric heater by disconnecting step by
step in the event of overload in a phase. It will be reconnected
if other current consumption is reduced.
Connecting current sensors
A current sensor (BE1 - BE3) should be installed on each
incoming phase conductor in to the electrical distribution unit
to measure the current. This is best done in the electrical
distribution unit.
Connect the current sensors to a multi-core cable in an
enclosure next to the electrical distribution unit. Use a multi-
core cable of at least 0.5 mm² from the enclosure to the heat
pump.
&RQQHFWWKHFDEOHWRWHUPLQDOEORFN;WR
; LV WKH FRPPRQ WHUPLQDO EORFN IRU WKH WKUHH FXUUHQW
sensors.
Set the size of the property's main fuse in menu 5.1.12.
Inkommande el
N
E
P
L
1
L
2
L
3
Värmepump
Control module
Incoming electricity
6
5
4
3
2
1
SMO
Externt
External
RC-HY 40
BE3
BE2
BE1
AA3-X4
RC-HY40
AA3-X4
Electrical distribution unit
Electrical distribution unit
Summary of Contents for FDCW60VNX-W
Page 2: ......
Page 77: ...75 Technical data Electrical circuit diagram HSB60 W ...
Page 78: ...76 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 79: ...77 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 80: ...78 Technical data RC HY RC HY RC HY ...
Page 83: ...81 Technical data sheet 3 ...
Page 84: ...82 Technical data sheet 4 ...
Page 87: ...85 Technical data sheet 3 ...
Page 88: ...86 Technical data sheet 4 ...
Page 89: ...87 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 90: ...88 Technical data sheet 6 ...
Page 91: ...89 MEMO ...