61
Control
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Make settings for the hot water comfort here.
See the accessory installation instructions for function
description.
activating imm heater:
The immersion heater is activated
here if installed in the water heater.
activ. imm heat in heat mode:
Activate here whether the
immersion heater in the tank (required if the alternative above
is activated) will be permitted to charge hot water, if the
compressors in the heat pump prioritise heating.
activating the mixing valve:
Activate here whether a mixer
valve for limiting the temperature of hot water from the water
heater is installed.
If this alternative has been activated, you can set the outgoing
KRWZDWHUWHPSHUDWXUHVKXQWDPSOL¿FDWLRQDQGVKXQWZDLWLQJ
time for the mixer valve.
outgoing hot water:
Set the temperature at which the
mixing valve is to restrict hot water from the water heater.
See the accessory installation instructions for function
description.
Menu 5.3.20 - flow sensor
EMK 500
flow sensor
flow sensor 5.3.20
flow sensor
Setting option: EMK 500, EMK 310 / 300, EMK 150
Factory setting: EMK 500
Here you select which flow sensor is used for the energy
measurement.
that you have selected. If this function is activated, you can set
FRROLQJIORZWHPSDW&DQGFRROLQJIORZWHPSDW
& IRU HDFK FOLPDWH V\VWHP ZKHUH WKH IXQFWLRQ LV
activated.
CAUTION
This setting option only appears if "cooling permitted" is
activated in menu 5.11.1.1.
7KHVKXQWDPSOL¿FDWLRQDQGVKXQWZDLWLQJWLPHIRUWKHGL൵HUHQW
extra climate systems that are installed are also set here.
See the accessory installation instructions for function
description.
Menu 5.3.6 - step controlled add. heat
start addition
Setting range: 0 – 2000 GM
Default values: 400 GM
diff. between additional steps
Setting range: 0 – 1000 GM
Default values: 30 GM
max step
Setting range
(binary stepping deactivated): 0 – 3
Setting range
(binary stepping activated): 0 – 7
Default value: 3
binary stepping
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
Make settings for step controlled addition here. Step controlled
addition is for example an external electric boiler.
It is possible, for example, to select when the additional heat is
to start, to set the maximum number of permitted steps and
whether binary stepping is to be used.
:KHQELQDU\VWHSSLQJLVGHDFWLYDWHGR൵WKHVHWWLQJVUHIHUWR
linear stepping.
See the accessory installation instructions for function
description.
Menu 5.3.8 - hot water comfort
activating imm heater
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
activ. imm heat in heat mode
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
activating the mixing valve
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
outgoing hot water
Setting range: 40 – 65 °C
Summary of Contents for FDCW60VNX-W
Page 2: ......
Page 77: ...75 Technical data Electrical circuit diagram HSB60 W ...
Page 78: ...76 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 79: ...77 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 80: ...78 Technical data RC HY RC HY RC HY ...
Page 83: ...81 Technical data sheet 3 ...
Page 84: ...82 Technical data sheet 4 ...
Page 87: ...85 Technical data sheet 3 ...
Page 88: ...86 Technical data sheet 4 ...
Page 89: ...87 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 90: ...88 Technical data sheet 6 ...
Page 91: ...89 MEMO ...