39
Electrical installation
AUX inputs
Up to 6 other external inputs are available on RC-HY40.
AUX1 through 3 correspond to the port 9/10, 11/12, 13/14
respectively on X6 terminal on AA3 board. AUX4 through 6
correspond to the port 1, 2 and 3 on X2 terminal on RC-HY40.
Port 4 on X2 terminal is GND and is common to AUX4
through 6. Connect a sensor or switch between AUX and GND
with a two-core cable with a minimum cross section of
0.5mm
2
.
AUX1
AUX2
AUX3
RC-HY40
AUX4
AUX5
GND
AUX6
AA3-X6
X2
Select the appropriate function in menu 5.4.
block heating
activate temp lux
not used
soft in/outputs
5.4
not used
not used
not used
Ŷ7HPSHUDWXUHVHQVRUH[WHUQDOVXSSO\DWDGGLWLRQDOKHDWEHIRUH
reversing valve (BT63)
Temperature sensor BT63 is applied in case additional heater
is placed before 3-way valve (see page 22 for diagram)
The following functions are available. For details, see AUX
inputs for RC-HY20.
Ŷ7HPSHUDWXUHVHQVRUFRROLQJKHDWLQJ%7
Ŷ7HPSHUDWXUHVHQVRUH[WHUQDOUHWXUQOLQH%7
Ŷ7HPSHUDWXUHVHQVRUÀRZOLQHFRROLQJ%7
Ŷ&RQWDFWIRUH[WHUQDOWDUL൵EORFNLQJ
Ŷ6ZLWFKIRU³6*UHDG\´
Ŷ&RQWDFWIRUDFWLYDWLRQRI³WHPSRUDU\OX[´
Ŷ&RQWDFWIRUDFWLYDWLRQRI³H[WHUQDODGMXVWPHQW´
Ŷ6ZLWFKIRUH[WHUQDODODUP
Ŷ6ZLWFKIRUH[WHUQDOEORFNLQJ
AUX outputs
External output is available on the port NC, NO and C on X7
terminal on AA3 board on RC-HY40. The relay output can
have a max load of 2A at resistive load.
Following functions are available. Select the function in menu
5.4.
Indication of buzzer alarm
When an alarm occurs, the circuit becomes closed between
the port NO and C. During normal operation, the port NC
and C is closed.
Cooling mode indication / Active cooling mode (4-pipe
cooling)
When the system turns into cooling mode, the circuit
becomes closed between the port NO and C. By using this
signal, it is possible to switch 3-way valve for 4-pipe cooling
or to assemble a display circuit indicating cooling mode. For
details of connecting the 3-way valve, refer to page 31.
External pump control (GP10)
External pump (GP10) is used in case additional heater is
placed after 3-way valve that switches heating/hot water
(refer to page 23 for diagram).
Connect the circulation pump using the port NO and C on
X7 terminal on AA3 board as shown below.
C
N
O
N
C
Externt
SMO
L
PE
N
N
PE
L
External
RC-HY 40
AA3-X7
AA3-X7
RC-HY40
myUpway
™
Connect the network connected cable (straight, Cat.5e UTP)
with RJ45-contact (male) to contact AA4-X9 on the display
unit (as illustrated). Use the cable grommet (UB2) in the
control module for cable routing.
AA4-X9
-
Summary of Contents for FDCW60VNX-W
Page 2: ......
Page 77: ...75 Technical data Electrical circuit diagram HSB60 W ...
Page 78: ...76 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 79: ...77 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 80: ...78 Technical data RC HY RC HY RC HY ...
Page 83: ...81 Technical data sheet 3 ...
Page 84: ...82 Technical data sheet 4 ...
Page 87: ...85 Technical data sheet 3 ...
Page 88: ...86 Technical data sheet 4 ...
Page 89: ...87 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 90: ...88 Technical data sheet 6 ...
Page 91: ...89 MEMO ...