60
Control
Symbol Description
Compressor (blocked)
Compressor (standard)
Reversing valves for hot water, cooling.
The designations above the reversing valve
indicate where it is electrically connected
(EB101 = Slave 1, etc.).
Hot water charging
Heating (heating the building, includes any
extra climate system)
Cooling
Menu 5.2.4 - accessories
Set which accessories are installed on the installation here.
If the water heater is connected, hot water charging must be
activated here.
Menu 5.3 - accessory settings
The operating settings for accessories that are installed and
activated are made in the sub-menus for this.
Menu 5.3.2 - shunt controlled add. Heat
prioritised additional heat
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
start diff additional heat
Setting range: 0 – 2000 GM
Default values: 400 GM
minimum running time
Setting range: 0 – 48 h
Default value: 12 h
min temp.
Setting range: 5 – 90 °C
Default value: 55 °C
mixing valve amplifier
Setting range: 0.1 –10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Set when the addition is to start, the minimum run time and the
minimum temperature for external addition with shunt here.
External addition with shunt is for example a wood/oil/gas/
pellet boiler.
<RXFDQVHWVKXQWYDOYHDPSOL¿FDWLRQDQGVKXQWYDOYHZDLWLQJ
time.
Selecting "prioritised additional heat" uses the heat from the
external additional heat instead of the heat pump.
The shunt valve is regulated as long as heat is available,
otherwise the shunt valve is closed.
See the accessory installation instructions for function
description.
Menu 5.3.3 - extra climate system
use in heating mode
6HWWLQJUDQJHRQR൵
Factory setting: on
use in cooling mode
6HWWLQJUDQJHRQR൵
)DFWRU\VHWWLQJR൵
mixing valve amplifier
Setting range: 0.1 – 10.0
Default value: 1.0
mixing valve step delay
Setting range: 10 – 300 s
Default values: 30 s
Here you select which climate system (2 - 8) you wish to set.
In the next menu you can make settings for the climate system
Summary of Contents for FDCW60VNX-W
Page 2: ......
Page 77: ...75 Technical data Electrical circuit diagram HSB60 W ...
Page 78: ...76 Technical data HMK60 RC HY FDCW60VNX A FDCW60VNX A 2 FDCW60VNX A 3 ...
Page 79: ...77 Technical data FDCW60VNX A 2 FDCW60VNX A 3 RC HY RC HY RC HY ...
Page 80: ...78 Technical data RC HY RC HY RC HY ...
Page 83: ...81 Technical data sheet 3 ...
Page 84: ...82 Technical data sheet 4 ...
Page 87: ...85 Technical data sheet 3 ...
Page 88: ...86 Technical data sheet 4 ...
Page 89: ...87 Technical data INDOOR UNIT HSB INDOOR UNIT HSB sheet 5 ...
Page 90: ...88 Technical data sheet 6 ...
Page 91: ...89 MEMO ...