4 - 11 4 - 11
4 SETUP AND PROCEDURES BEFORE OPERATION
MELSEC-Q
1 The mode switching (normal mode to offset/gain setting mode to normal mode)
method is given below.
Dedicated instruction (G.OFFGAN)
Refer to Section 4.6 (2), (a)
Setting made to mode switching setting (buffer memory addresses 158, 159:
Un\G158, Un\G159) and turning the Operating condition setting request (Y9)
from OFF to ON Refer to Section 4.6 (2), (b)
Intelligent function module switch setting Refer to Section 4.5, Section 4.6
(2), (c)
(After intelligent function module switch setting, reset the programmable
controller CPU or switch power OFF, then ON.)
2 Do not perform the following during the steps marked 2.
If any of the following is performed, the data in E
2
PROM will have a problem and
the Q64RD/Q64RD-G may not operate normally.
• Powering off the programmable controller CPU
• Resetting the programmable controller CPU