![Mitsubishi Electric Q64RD User Manual Download Page 28](http://html.mh-extra.com/html/mitsubishi-electric/q64rd/q64rd_user-manual_238785028.webp)
3 - 1 3 - 1
MELSEC-Q
3 SPECIFICATIONS
3 SPECIFICATIONS
3.1 Performance Specifications
The following are the performance specifications of the Q64RD/Q64RD-G.
3.1.1 Specifications of Q64RD
Item Specifications
Number of channels
4 channels
Output
Measured
temperature value
16-bit, signed binary data (-2000 to 8500: Value to the first decimal place 10)
32-bit, signed binary data (-200000 to 850000: Value to the third decimal place 1000)
Scaling value
16-bit, signed binary
Usable platinum RTD
Pt100(JIS C 1604-1997,IEC 751 1983), JPt100(JIS C 1604-1981)
Measured
temperature
range
Pt100
-200 to 850
JPt100
-180 to 600
Range
changing
Pt100
-20 to 120 / -200 to 850
JPt100
-20 to 120 / -180 to 600
Accuracy
1
Ambient temperature
0 to 55
0.25% (Accuracy relative to maximum value)
Ambient temperature
25 5
0.08% (Accuracy relative to maximum value)
Resolution
0.025
Conversion speed
40ms/channel
2
Number of analog input channels
4 channels/module
Temperature detecting output current
1mA
E
2
PROM write count
Max. 100,000 times
Isolation
Specific isolated area
Isolation
method
Dielectric
withstand voltage
Isolation
resistance
Between platinum temperature-
measuring resistor input and
programmable controller power supply
Photocoupler
isolation
1780VrmsAC/
3 cycles
(Altitude 2000m)
10M or more
using 500VDC
isolation
resistance tester
Between platinum temperature-
measuring resistor input channels
No isolation
-
Wire break detection
Yes (Each channel independent)
3
Number of occupied I/O points
16 points (I/O assignment: Intelligent 16 points)
External interface
18-point terminal block
Applicable wire size
0.3 to 0.75mm
2
Applicable crimping terminals
1.25-3 R1.25-3 (Sleeved crimping terminals are unusable)
Cables between Q64RD and platinum
RTD
Refer to Section 3.1.3.
Internal current consumption (5VDC)
0.60A
Weight
0.17kg
Outline dimensions
98(H) 27.4(W) 90(D)mm
1: The selection ranges and accuracies have the following relationships.
Selection Range
Ambient Temperature
Pt100 and JPt100 :
-20 to 120
Pt100 :
-200 to 850
JPt100 :
-180 to 600
0 to 55
0.3
2.125
1.5
25 5 0.096
0.68
0.48
2: The conversion speed is a period from when a temperature is input and converted into a corresponding digital value until the value is
stored into the buffer memory.
When two or more channels are used, the conversion speed is "40ms number of conversion enabled channels".
3: For output in the case of disconnection detection, select any of "Value immediately before disconnection", "Up scale (maximum value
of measured temperature range + 5% of measured temperature range)", "Down scale (minimum value of measured temperature
range – 5% of measured temperature range)" or "Given value". (Refer to Section 3.2.2.)