![Mitsubishi Electric Q64RD User Manual Download Page 149](http://html.mh-extra.com/html/mitsubishi-electric/q64rd/q64rd_user-manual_238785149.webp)
7 - 35 7 - 35
7 ONLINE MODULE CHANGE
MELSEC-Q
7.4 Range Reference Table
7.4.1 Range reference table (Q64RD)
The range reference tables for the Q64RD are given below.
Address (Decimal)
Description Reference
value
CH1 CH2 CH3 CH4
160 184 208 232
3-wire type factory default offset value
1
Factory-set offset digital value (Reference value: 3B1D
H
)
161 185 209 233
3-wire type factory default offset value
1
Factory-set offset digital value (Reference value: 3B1D
H
)
162 186 210 234
3-wire type factory default gain value
1
Factory-set gain digital value (Reference value: B158
H
)
163 187 211 235
3-wire type factory default gain value
1
Factory-set gain digital value (Reference value: B158
H
)
164 188 212 236
3-wire type User range setting offset value
1
Digital value for user-set offset value (Refer to (3).)
165 189 213 237
3-wire type User range setting offset value
1
Digital value for user-set offset value (Refer to (4).)
166 190 214 238
3-wire type User range settings gain value
1
Digital value for user-set gain value (Refer to (5).)
167 191 215 239
3-wire type User range settings gain value
1
Digital value for user-set gain value (Refer to (6).)
168 192 216 240
3-wire type User range settings offset resistance value
(L)
Resistance value for user-set offset set temperature
(
10
-2
)
169 193 217 241
(H)
170 194 218 242
3-wire type User range settings gain resistance value
(L)
Resistance value for user-set gain set temperature
(
10
-2
)
171 195 219 243
(H)
172 196 220 244
4-wire type factory default offset value
1
Factory-set offset digital value (Reference value: 3B1D
H
)
173 197 221 245
4-wire type factory default offset value
1
Factory-set offset digital value (Reference value: 3B1D
H
)
174 198 222 246
4-wire type factory default gain value
1
Factory-set gain digital value (Reference value: B158
H
)
175 199 223 247
4-wire type factory default gain value
1
Factory-set gain digital value (Reference value: B158
H
)
176 200 224 248
4-wire type User range setting offset value
1
Digital value for user-set offset value (Refer to (3).)
177 201 225 249
4-wire type User range setting offset value
1
Digital value for user-set offset value (Refer to (4).)
178 202 226 250
4-wire type User range settings gain value
1
Digital value for user-set gain value (Refer to (5).)
179 203 227 251
4-wire type User range settings gain value
1
Digital value for user-set gain value (Refer to (6).)
180 204 228 252
4-wire type User range settings offset resistance value
(L)
Resistance value for user-set offset set temperature (
10
-2
)
181 205 229 256
(H)
182 206 230 254
4-wire type User range settings gain resistance value
(L)
Resistance value for user-set gain set temperature (
10
-2
)
183 207 231 255
(H)
1: There are two identical areas consecutively. (Buffer memory addresses 160, 161 both have the 3-wire type CH. 1 factory default offset values.) Set the
same value in each area.
(1) Compare the factory default offset value with the reference value 3B1D
H
.
(2) Compare the factory default gain value with the reference value B158
H
.
(3) Compare the user range settings offset value with the value obtained by the
following formula
Digital value = User range settings offset resistance value ( 10
-2
)
1.51336
(4) Compare the user range settings gain value with the value obtained by the
following formula
Digital value = User range settings gain resistance value ( 10
-2
)
1.51336