4 - 7 4 - 7
4 SETUP AND PROCEDURES BEFORE OPERATION
MELSEC-Q
4.5 Switch Setting for Intelligent Function Module
The settings for the intelligent function module are performed using the I/O assignment
settings for GX Developer.
(1) Setting item
The intelligent function module switches consist of switches 1 to 5 and are set
using 16 bit data. When the intelligent function module switches are not set, the
default value for switches 1 to 5 is 0.
Setting
Item
Switch 1
Measurement range setting
Measurement mode
Measurement range
Set value 1
New JIS
(Pt 100)
-200 to 850
0
-20 to 120
1
0 to 200
4
Old JIS
(JPt100)
-180 to 600
2
-20 to 120
3
0 to 200
5
Ni100
-60 to 180
8
Switch 2
Offset/gain setting
Offset/gain setting
Set value
Factory
default
0
User range setting
1
Switch 3
Wiring type setting
Wiring type setting
Set value
3-wire
type
0
4-wire
type
1
Switch 4
Switch 5
0: Fixed
1 The setting range 0 to 3 is available for the Q64RD/Q64RD-G. Setting of 4, 5 and 8 is available for the Q64RD-G only.
Setting other than these setting values will output an error. For details, check the error code.
2 The same operation is activated with any value within the setting range. For the range of 1
H
to F
H
, for example, set 1.
CH4 CH3 CH2 CH1
H
CH4 CH3 CH2 CH1
H
CH4 CH3 CH2 CH1
H