![Mitsubishi Electric Q64RD User Manual Download Page 53](http://html.mh-extra.com/html/mitsubishi-electric/q64rd/q64rd_user-manual_238785053.webp)
3 - 26 3 - 26
3 SPECIFICATIONS
MELSEC-Q
3.4.3 Conversion enable/disable setting (Un\G0)
(1) You can make setting to enable/disable temperature conversion on each channel.
(2) Specifying unused channels as "conversion disabled" prevents unnecessary
disconnection detection and also reduces sampling time.
(3) At power-on or reset, the conversion enable/disable setting is set to 000F
H
(all
channels disabled).
[Example]
(4) The Operating condition setting request (Y9) must be turned on/off to make the
conversion enable/disable setting valid.
3.4.4 CH time/count/moving average/time constant setting (Un\G1 to 4)
(1) For each channel for which Averaging processing specification (buffer memory
address 9: Un\G9) and Extended averaging processing specification (buffer
memory address 134: Un\G134) is made, set the averaging time, averaging count,
the number for moving average or time constant for primary delay filter.
(2) Allowable setting range is as follows:
Processing method
Set value
Time averaging
160 to 5000 (ms)
Count averaging
4 to 62500 (times)
1
Moving average
4 to 60 (times)
Primary delay filter
40 to 5000 (ms)
Setting any value outside the above range will result in an error and the operation
will be performed under the previous setting.
1 When setting 32768 times or more in the sequence program, set the count
in hexadecimal. For instance, set F42
H
to specify 62500 times.
(3) This setting will be invalid if sampling is specified for Averaging processing
specification (buffer memory address 9: Un\G9) or Extended averaging
processing specification (buffer memory address 134: Un\G134).
(4) At power-on or reset, this is preset to 0000
H
. Change the setting according to the
processing method.
(5) The Operating Condition Setting Request (Y9) must be turned on/off to make this
setting valid.
(6) Refer to Section 3.4.5 and 3.4.21 for further details.
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
CH4 CH3 CH2 CH1
0: Conversion enabled
1: Conversion disabled
0
0
0
0
0
0
0
0
b15 b14 b13 b12 b11 b10
b9
b8
b7
b6
b5
b4
b3
b2
b1
b0
0
0
0
0
1
1
0
0
Channels 1 and 2 are conversion enabled.
0
0
0
0
0
0
0
0
Summary of Contents for Q64RD