7 - 27 7 - 27
7 ONLINE MODULE CHANGE
MELSEC-Q
(4) Operation
check
(a) To make an operation check, click the [Cancel] button to cancel control
resumption.
(b) Click the [OK] button to leave the "Online module change" mode.
(c) Click the [Close] button to close the System monitor screen.
(d) Enable the conversion of the channel to be used through conversion
enable/disable setting (buffer memory address 0: Un\G0), and monitor CH
measured temperature values (16 bits) (buffer memory addresses 11 to
14: Un\G11 to 14) or CH measured temperature values (32 bits) (buffer
memory addresses 54 to 61: Un\G54 to 61) to check that proper conversion
has been made.