![Mitsubishi Electric Q64RD User Manual Download Page 151](http://html.mh-extra.com/html/mitsubishi-electric/q64rd/q64rd_user-manual_238785151.webp)
7 - 37 7 - 37
7 ONLINE MODULE CHANGE
MELSEC-Q
7.4.2 Range reference table (Q64RD-G)
The range reference tables for the Q64RD-G are given below.
Address (Decimal)
Description Reference
value
CH1 CH2 CH3 CH4
160
184
208
232
3-wire type factory default offset value (L)
Factory-set offset digital value (Reference value: 1E2FEE
H
)
161
185
209
233
3-wire type factory default offset value (H)
162
186
210
234
3-wire type factory default gain value (L)
Factory-set gain digital value (Reference value: 5A8FCA
H
)
163
187
211
235
3-wire type factory default gain value (H)
164
188
212
236
3-wire type User range setting offset value (L)
Digital value for user-set offset value (Refer to (3).)
165
189
213
237
3-wire type User range setting offset value (H)
166
190
214
238
3-wire type User range settings gain value (L)
Digital value for user-set gain value (Refer to (4).)
167
191
215
239
3-wire type User range settings gain value (H)
168 192 216 240
3-wire type User range settings offset resistance value
(L)
Resistance value for user-set offset set temperature
(
10
-2
) (Refer to (5).)
169 193 217 241
(H)
170 194 218 242
3-wire type User range settings gain resistance value
(L)
Resistance value for user-set gain set temperature
(
10
-2
) (Refer to (6).)
171 195 219 243
(H)
172
196
220
244
4-wire type factory default offset value
(L)
Factory-set offset digital value (Reference value: 1E2FEE
H
)
173
197
221
245
4-wire type factory default offset value
(H)
174
198
222
246
4-wire type factory default gain value
(L)
Factory-set gain digital value (Reference value: 5A8FCA
H
)
175
199
223
247
4-wire type factory default gain value
(H)
176
200
224
248
4-wire type User range setting offset value
(L)
Digital value for user-set offset value (Refer to (3).)
177
201
225
249
4-wire type User range setting offset value
(H)
178
202
226
250
4-wire type User range settings gain value
(L)
Digital value for user-set gain value (Refer to (4).)
179
203
227
251
4-wire type User range settings gain value
(H)
180 204 228 252
4-wire type User range settings offset resistance value
(L)
Resistance value for user-set offset temperature (
10
-2
)
(Refer to (5).)
181 205 229 253
(H)
182 206 230 254
4-wire type User range settings gain resistance value
(L)
Resistance value for user-set gain temperature (
10
-2
)
(Refer to (6).)
183 207 231 255
(H)
(1) Compare the factory default offset value with the reference value 1E2FEE
H
.
(2) Compare the factory default gain value with the reference value 5A8FCA
H
.
(3) Compare the user range settings offset value with the value obtained by the
following formula
Digital value = User range settings offset resistance value ( 10
-2
)
197.835
(4) Compare the user range settings gain value with the value obtained by the
following formula
Digital value = User range settings gain resistance value ( 10
-2
)
197.835
(5) Obtain a reference resistance value that corresponds to the offset setting
temperature set by the user from the chart of reference resistance value that is
compliant with JIS C 1604-1997 or IEC 751 1983, JIS C 1604-1981, or DIN
43760 1987. Compare the value with the user range settings offset resistance
value.