3.4.23 CH Conversion setting value for disconnection detection (Un\G150 to 157)
(1) If Given value (3
H
) is set in the Conversion setting for disconnection detection
(buffer memory address 148: Un\G148), when disconnection is detected, the
value set in this area is stored in the CH measured temperature value (buffer
memory addresses 11 to 14, 54 to 61: Un\G11 to 14, Un\G54 to 61).
If any of 0
H
to 2
H
is set in the Conversion setting for disconnection detection,
setting of this area is ignored.
(2) The setting range is from –2147483648 to 2147483647 (0000
H
to FFFFFFFF
H
).
(Setting in 0.001 increments.)
[Example] To set to 0.3 ..... Store 300.
(3) This is set to 0 when the module is powered up or reset.
(4) The Operating Condition Setting Request (Y9) must be turned on/off to make the
setting valid.
3.4.24 Mode switching setting (Un\G158 to 159)
(1) Set the values of the mode to which you want to switch.
(2) After setting the values, turning the operating condition setting request (Y9) from
OFF to ON switches the mode.
(3) When mode switching is performed, this area is cleared to zero and the operating
condition setting completion signal (X9) turns OFF.
After confirming that the this signal (X9) has turned OFF, turn OFF the operating
condition setting request (Y9).
Mode to be switched to
Set values
Buffer memory address 158 Buffer memory address 159
Normal mode
0964
H
4144
H
Offset/gain setting mode
4144
H
0964
H
POINT
If the values written are other than the above, mode switching is not performed and
only the operating condition is changed.
Summary of Contents for Q64RD
Page 2: ......
Page 99: ...5 17 5 17 5 UTILITY PACKAGE GX Configurator TI MELSEC Q X Y Monitor Test 1 OMC refresh ...
Page 113: ...6 8 6 8 6 PROGRAMMING MELSEC Q 2 Program example ...
Page 114: ...6 9 6 9 6 PROGRAMMING MELSEC Q ...
Page 181: ...WARRANTY ...
Page 183: ......