8 TROUBLESHOOTING
Error Code
(Decimal)
Description Remedy
6
1
The set warning output upper/lower limit value is outside the
measurable temperature range specified for the used
platinum temperature-measuring resistor.
indicates the channel number set incorrectly.
indicates any of the following statuses.
0: The lower lower limit value is lower than the
measurement range.
1: The upper upper limit value is higher than the
measurement range.
2: Lower lower limit value > lower upper limit value
3: Lower upper limit value > upper lower limit value
4: Upper lower limit value > upper upper limit value
Set a correct value at the buffer memory address 86 to 117
(Un\G86 to 117). (Refer to Section 3.4.19.)
POINT
If two or more errors have occurred, the code of the error found by the
Q64RD/Q64RD-G first is stored. The latter errors are not stored.
The errors marked 1 can be cleared by turning on the error clear request (YF).
The error marked 2 is not written to the buffer memory address 19 (Un\G19). It
is written to the completion status area (S) + 1 of the G(P).OGSTOR instruction.
If mode switching is performed, an error is cleared.