2
B
A
A
B
C
D
e
a
b
c
d
C
C
C
C
C
B
A
a
b
c
d
C
D
C
C
C
C
C
e
A
A
: Outdoor Unit
B
: First Branch
C
: Indoor unit
D
: Cap
4
[Fig. 4.0.1]
a, b, c, d, e
(mm)
Î
Model number
Å
Liquid pipe
ı
Gas pipe
20,25,32,40
ø6.35
ø12.7
50,63,71,80
ø9.52
ø15.88
100,125,140
ø9.52
ø19.05
200
ø12.7
ø25.4
250
ø12.7
ø28.58
<A>
A
L
2
=
>
L
1
=
>
(1)
<A> : Top view
<B> : Side view
<C> : When there is little space up to an obstruction
A
: Front
B
: No restrictions on wall height (left and right)
C
: Air outlet guide (Procured at the site)
(mm)
L
1
L
2
450
450
A
A
F
A
L
1
=
>
L
1
=
>
D
: Must be open
E
: Wall height (H)
F
: No restrictions on wall height
7
7.2
[Fig. 7.2.1]
E
A
A
D
D
E
L
2
=
>
L
1
=
>
1000
=
>
E
D
E
A
A
A
A
A
L
1
=
>
L
1
=
>
L
1
=
>
L
1
=
>
L
1
=
>
L
2
=
>
E
A
A
E
D
D
1000
=
>
L
2
=
>
L
2
=
>
900
=
>
E
A
D
A
D
1000
=
>
1000
=
>
900
L
2
=
>
=
>
(5)
<C>
<B>
(2)
C
45
°
=
>
300
=
>
1000
=
>
(3)
<A>
<B>
A
A
B
Hh
L
2
=
>
L
1
=
>
L
1
=
>
L
2
=
>
(4)
A
650
325
A
H
h
Hh
L
1
=
>
L
1
=
>
L
2
=
>
L
2
=
>
<A>
<B>
6
[Fig. 6.1.1]
B
A
A
: M10 anchor bolt procured at the site.
B
: Corner is not seated.
[Fig. 5.0.1]
5
40
°
=
<
7m
= <
7m
= <
B, C, D
(mm)
Ç
Total capacity of indoor units
Å
Liquid pipe
ı
Gas pipe
~ 80
ø9.52
ø15.88
81 ~ 160
ø12.7
ø19.05
161 ~
ø12.7
ø25.4
‰
Downstream Unit Model Total
Ï
Branch Kit Model
~ 160
CMY-Y102S-F
161 ~
CMY-Y102L-F
Ì
4-Branching Header
Ó
7-Branching Header
È
10-Branching Header
CMY-Y104-F
CMY-Y107-F
CMY-Y1010-F
A
(mm)
Å
Liquid pipe
ı
Gas pipe
PUHY-P200
ø12.7
ø25.4
PUHY-P250
ø12.7
ø28.58