67
Example of Simple Set-up
A simple set-up example is shown below.
Set it to
P01
and press .
SET
Model type: ME96NSR (with ME-4201-NS96 optional plug-in module)
Phase wire: Three phase 4-wire Voltage display: Phase to phase
Measurement items: A, V, W, PF
Input voltage: 220V/380V direct
Primary current: 200A
Secondary current: 5A
Active power maximum scale: 160kW (standard: rating 100%)
Analog output: CH1(A
AVG
), CH2(V
AVG(L-N)
), CH3(
Σ
W, 160kW), CH4(
Σ
PF, 0.5 to 1 to 0.5)
Pulse output: Imported active energy, Pulse unit: 10kW/pulse
■
Set-up example
Items that require set value change are shown in shade.
■
Set-up procedures
SET
SET
SET
SET
SET
SET
RESET
Pressing simultaneously for 2 seconds
Operation mode
Secondary current
Direct voltage
Display pattern
Phase wire
Set-up menu
Set the set-up menu number to
1
and press .
SET
It is set to
no (direct input)
at initial content, so press as it is.
SET
Using VT or
direct input
It is set to
3P4 (Three phase 4-wire)
at initial content, so press as it is.
SET
It is set to
220/380V
at initial content, so press as it is.
SET
It is set to
5A
at initial content, so press as it is.
SET
SET
SET
SET
SET
Set-up menu
Time constant of
current demand
Primary current
It is set to
0s
at initial content, so press as it is.
SET
Set the set-up menu number to
7
and press .
SET
Set it to
200A
and press .
SET
+
–
,
+
–
,
+
–
,
+
–
,
+
–
,
+
–
,