63
Optional Plug-in Module : ME-0040C-NS96
1. As for CC-Link cable, use the designated cable. Each of Ver.1.10 compatible CC-Link
cables, CC-Link dedicated cables, and CC-Link dedicated high-performance cables can-
not be used together with other cable types. If used together, correct data transmission
will not be guaranteed.
The terminating resistor is different depending on the applied cable.
2. Connect the shielded wire of the CC-Link dedicated cable to “SLD” of each module, and
earth the both ends of the shielded wire via “FG”. The SLD and FG are connected into the
module.
3. Keep the distance between CC-Link cables to power lines.
(Refer to Installation instruction in Safety Precaution.)
4. Fill the requirements of total wire distance, station distance, and terminal resistance value
according to baud rate and type of cable.
(As for detail of the requirements, refer to the operation manual for CC-Link master unit.)
5. To the units of both the end of CC-Link line, the terminal resistors should be attached.
And the terminal resistors should be attached in between DA and DB.
Terminal registers are accessories of CC-Link master unit.
Note
Installation 4. Wiring Diagram