31
4.9 Simplified Set-up
!6
Communication
module reset
+
–
,
0: OFF
1: ON
Set-up menu
q
Phase wire
1:3P3W (2CT)
2:3P3W (3CT)
3:3P4W
t
VT secondary
voltage
[3P4W]
1:63.5V
2:100V
3:110V
4:115V
5:120V
[3P3W]
1:100V
2:110V
3:220V
!2
ModBus
parity
0:non
1:odd
2:EVEn
w
Display pattern
00:P00 11:P11
01:P01 12:P12
02:P02 13:P13
03:P03
04:P04
05:P05
06:P06
07:P07
08:P08
09:P09
10:P10
r
Direct voltage
[3P4W]
1:63.5V/110V
2:100V/173V
3:110V/190V
4:220V/380V
5:240V/415V
6:254V/440V
7:277V/480V
[3P3W]
1:110V
2:220V
e
Using VT
/direct input
0:direct input
1:using VT
o
Communication
method
1:CC-Link
2:ModBus
!1
ModBus
baud rates
1:2400bps
2:4800bps
3:9600bps
4:19.2kbps
5:38.4kbps
!0
ModBus
address
001 to 255
According to the set-up diagram (page 13), save the changed
contents or continue to the other set-up menu.
+
–
,
SET
!3
ModBus
stop bit
1:1
2:2
!4
CC-Link
station
number
01 to 64
!6
Communication
module reset
0:OFF
1:ON
!5
CC-Link
Baud rates
1:156kbps
2:625kbps
3:2.5Mbps
4:5Mbps
5:10Mbps
y
VT primary voltage
[Exponent value]
0:60 to 999V
1:1000 to 9990V
2:10000 to 99900V
3:100000 to 750000V
[Voltage value]
(100 digits) (10 digits) (1 digit)
0 to 9
0 to 9
0 to 9
u
CT primary current
[Exponent value]
0:5.0 to 9.9A
1:10 to 99A
2:100 to 990A
3:1000 to 9900A
4:10000 to 30000A
[Current value]
(10 digits) (1 digit)
0 to 9
0 to 9
i
Time constant
for current
demand
00:0s
10:5min
01:10s
11:6min
02:20s
12:7min
03:30s
13:8min
04:40s
14:9min
05:50s
15:10min
06:1min 16:15min
07:2min 17:20min
08:3min 18:25min
09:4min 19:30min
!6
Set the communication module reset.
In the case of ModBus, this content cannot be set.
Set it ON.
■
Simplified Set-up contents list
<Setting page: P-1>
<Setting page: P-2>
4. Set-up