58
Installation 3. Wiring
1 Applicable cable size
The below table describes the applicable wire size.
Applicable wire size
Fastening torque
Strip Gauge
Input and output terminals
of the basic device
AWG 24 to 14
0.4 N•m
10mm
Terminals of the
optional plug-in module
AWG 24 to 14
When using a stranded wire,
use a ferrule. (AWG 16)
----
10mm
2 Wiring
■
Input and output terminals of the basic device
q
Strip the top of the cables or crimp the ferrule.
w
Slacken screws of the terminal block, and insert the cables into terminal hole.
e
Fasten the terminal screws by the regulation fastening torque.
■
Terminals of the optional plug-in module
q
Strip the top of the cables or crimp the ferrule.
w
Insert the cables with pushing the lever, and connect by releasing the lever.
Insert hole
Lever
3 Confirmations
After wiring, make sure the followings:
M
The wires are wiring certainly.
M
There is no mistake in wiring.