17
4. Set-up
Set-up menu
DISPLAY
SET
DISPLAY
SET
1
Communication
method
Set the set-up menu number to “2”. (Set as shown in the right
display.)
1
Set the “CC-Link” or “ModBus” as the communication
method.
This display appears only if the type of ME96NSR-MB has
the type of ME-0040C-NS96 optional plug-in module.
CC
485
:
:
2
ModBus address
2
Set the ModBus address number.
In the case of CC-Link, this display does not appear.
Settable addresses: 1 to 255
3
ModBus
baud rates
3
Set the ModBus baud rate.
In the case of CC-Link, this display does not appear.
2400 bps
4800 bps
9600 bps
19.2 kbps
38.4 kbps
Stop bit : 1
Stop bit : 2
+
–
,
+
–
,
5
ModBus stop bit
5
Set the ModBus stop bit.
In the case of CC-Link, this display does not appear.
+
–
,
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
4
ModBus parity
4
Set the ModBus parity.
In the case of CC-Link, this display does not appear.
Settable parity:
non
odd
EVEn
Settable baud rate:
+
–
,
+
–
,
+
–
,
CC-Link
ModBus
Set-up Menu 2
4.3 Communication, Cancel of Digital Input Set-up
In the operation mode, press the
SET
and the
RESET
simultaneously for 2 seconds or more, and the following
operation becomes available.