35
When the ME-4201-NS96 type optional plug-in module is installed, simulated signal output to test the pulse output
circuit can be put out.
Operate it according to the following.
The following operation becomes possible when you turn on the power supply while pressing the
DISPLAY
at the
state of power failure.
It is impossible to test without the optional plug-in module.
5.4 Pulse Output Test
Test menu
SET
SET
SET
Set the test menu number to “3”. (Set as shown in the right
display.)
Test menu
In case of test the other output, according to the 5.2 to 5.5,
continue to the test.
When the test is finished, turn off the power supply.
+
–
,
+
–
,
q
Pulse output
CH1 test
+
–
,
w
Pulse output
CH2 test
+
–
,
q
Test the pulse output CH1.
When the , is pressed, the display and the pulse
output are changed as following.
+
–
oFF
(Opened)
on
(Closed)
q
Test the pulse output CH2.
When the , is pressed, the display and the pulse
output are changed as following.
+
–
oFF
(Opened)
on
(Closed)
5. Output Adjustment and How to Test