62
Installation 4. Wiring Diagram
Optional Plug-in Module : ME-4201-NS96
Optional Plug-in Module : ME-0052-NS96
1. Do not bunch the digital input/output signal cables with the main circuit or power cables,
or install them close to each other. Keep the distance between the digital input/output
signal cables and the main circuit or power cables, and high voltage lines are shown
below, when they run parallel to each other.
2. Analog output signal cables should keep the distance from the other power cables and
input signal (VT, CT and auxiliary power) cables, and should not bunch them. And use
the shielded cables or twisted pair cables not to be affected the noise, serge and induction.
Also, the wiring cables are to be as short as possible.
3. In case of ME96NSR-MB with ME-4201-NS96, the ModBus interface and the analog
outputs do not have the insulation between them.
Note
Conditions
Length
Below 600V power lines
Other power lines
30cm or more
60cm or more
ME-4201-NS96
ME96NSR
CH1+
CH1ー
CH2+
CH2ー
CH3+
CH3ー
CH4+
CH4ー
C1A
C1B
C2A
C2B
A
COM
Analog output CH1
Analog output CH2
Analog output CH3
Analog output CH4
Pulse output1
Pulse output2
{
{
{
{
{
{
{
Alarm output
DI1ー,DI2ー,DI3ー,DI4ー,DI5ー
are connected inside.
ME-0052-NS96
ME96NSR-MB
DI1+
DI1ー
DI2+
DI2ー
DI3+
DI3ー
DI4+
DI4ー
DI5+
DI5ー
DO1+
DO1ー
DO2+
DO2ー
DC24V
DO1
DO2
{
{
C
R
R
DI1+
DI1ー
DI5+
DI5ー