28
No.
q
w
e
r
Content
Phase wire
Display pattern
Using VT/direct input
Direct voltage
No.
t
y
u
i
Content
VT secondary voltage
VT primary voltage
CT primary current
Time constant for current demand
Simplified setting page: P-1
No.
o
!0
!1
!2
Content
Communication method
ModBus address
ModBus baud rates
ModBus parity
No.
!3
!4
!5
!6
Content
ModBus stop bit
CC-Link station number
CC-Link baud rates
Communication module reset
Simplified setting page: P-2
The setting contents of the main 16 items can be set by using two displays. It is set by the method of substituting the
numerical value.
For the setting contents, refer to the following table.
4. Set-up
4.9 Simplified Set-up
+
–
,
+
–
,
+
–
,
+
–
,
Set-up menu
DISPLAY
DISPLAY
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
DISPLAY
SET
1
Phase wire
Set the set-up menu number to “End”. (Set as shown in the right
display.)
Press the PHASE and the DISPLAY simultaneously for 1 second
or more.
1
Set the phase wire.
1 : 3P3W 2CT
2 : 3P3W 3CT
3 : 3P4W
00 : P00
to
13 : P13
0 : direct input.
1 : using VT
2
Display pattern
2
Set the display pattern.
3
Using VT/
direct input
3
Set the using VT or direct input (without VT).
+
–
,
[3P3W]
1 : 110V
2 : 220V
[3P4W]
1 : 63.5/100V
2 : 100/173V
3 : 110/190V
4 : 220/380V
5 : 240/415V
6 : 254/440V
7 : 277/480V
4
Direct voltage
4
Set the rated voltage for scaling for the bar graph.
If you set “1: using VT” on set up No.
3
, this content cannot
be set.
PHASE
+
For 1 secend or more
In the operation mode, press the
SET
and the
RESET
simultaneously for 2 seconds or more, and the following
operation becomes available.
By pressing
PHASE
key in the simplified set-up mode, the simplified setting page is changed.