5 SYSTEM CONFIGURATION
5.1 Configuration of PROFIBUS-DP network
41
5
Maximum configuration when one repeater is connected
Up to 32 modules can be connected in one segment.
DP-Master (FX5-DP-M): 1
DP-Slave: 61
Repeater: 1
*1 Any FDL address can be assigned to the DP-Master.
No.: FDL address (1 to 61 are for DP-Slaves, and 0 is for DP-Master)
*1
(1) Segment
(2) Bus terminator
(3) Repeater
FX5-DP-M
No.0
(2)
(2)
No.1
No.30
(2)
(3)
(1)
(2)
No.31
No.61