40
5 SYSTEM CONFIGURATION
5.1 Configuration of PROFIBUS-DP network
5
SYSTEM CONFIGURATION
5.1
Configuration of PROFIBUS-DP network
This section describes the basic configuration of the PROFIBUS-DP network using the FX5-DP-M as DP-Master (Class 1).
To configure the PROFIBUS-DP network, following conditions should be met.
*1 Includes the FX5-DP-M.
*2 Repeaters are counted as modules for both segments.
Maximum configuration when repeaters are not connected
Up to 32 modules can be connected in one segment.
DP-Master (FX5-DP-M): 1
DP-Slave: 31
*1 Any FDL address can be assigned to the DP-Master.
Configuration condition
Description
Number of connectable modules in the entire
network (when repeaters are used)
DP-Master
+ DP-Slave
≤
126
Number of connectable modules per segment
DP-Master
+ DP-Slave + Repeater
≤
32
Number of repeaters
Maximum of 3 repeaters between the FX5-DP-M and a DP-Slave
Number of connectable DP-Slaves per FX5-DP-M
64
No.: FDL address (1 to 31 are for DP-Slaves, and 0 is for DP-Master)
*1
(1) Segment
(2) Bus terminator
FX5-DP-M
No.0
(1)
(2)
(2)
No.1
No.31
Summary of Contents for FX5-DP-M
Page 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Page 13: ...11 CONTENTS ...
Page 19: ...1 DESCRIPTION 17 1 MEMO ...
Page 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Page 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Page 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Page 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Page 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Page 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Page 175: ......