4 FUNCTIONS
4.3 PROFIBUS-DPV1
33
4
Execution of the alarm acquisition function
The procedure for execution the Alarm acquisition function (Alarm read request without ACK) and Alarm ACK request.
For a program example of the alarm acquisition function, refer to the following.
Page 111 Program Example of the Alarm Acquisition Function
1.
When an alarm occurs, the DIA LED turns on and bit corresponding to the DP-Slave where the alarm is occurring turns
on in 'Slave status area (Alarm detection)' (Un\G26416 to Un\G26420). (
Page 155 Slave status area (Alarm
2.
Write Alarm read request (without ACK) to 'Alarm request area' (Un\G26432 to Un\G26434).
(
3.
Turn on 'Alarm read request signal' (Un\G3.b8).
4.
Alarms are acquired and the results are stored in 'Alarm response area' (Un\G26446 to Un\G26768).
(
Page 157 Normal response format when the alarm is read (without ACK))
5.
'Alarm read response signal' (Un\G1.b8) turns on. Check the alarm stored in 'Alarm response area' (Un\G26446 to
Un\G26768) and turn off 'Alarm read request signal' (Un\G3.b8).
6.
Write Alarm ACK request to 'Alarm request area' (Un\G26432 to Un\G26434).
7.
Turn on 'Alarm read request signal' (Un\G3.b8).
8.
ACK is returned and the results are stored in 'Alarm response area' (Un\G26446 to Un\G26768). (
response format for alarm ACK)
9.
If ACK is returned for all alarms of the DP-Slave, the corresponding bit in 'Slave status area (Alarm detection)'
(Un\G26416 to Un\G26420) and the DIA LED turn off. If ACK is not returned for some alarms, the corresponding bit and
the DIA LED remain on.
10.
'Alarm read response signal' (Un\G1.b8) turns on. Check the alarm stored in 'Alarm response area' (Un\G26446 to
Un\G26768) and turn off 'Alarm read request signal' (Un\G3.b8).
DIA LED turns off when ACK is returned for all alarms if all of the following conditions are met.
• Bits of all DP-Slaves are off in 'Slave status area (Alarm detection)' (Un\G26416 to Un\G26420).
• Bit 11 is off for status 1 in 'Diagnostic information area' (Un\G23072 to Un\G23199).
BF LED turns off when ACK is returned for all alarms if all of the following conditions are met.
• Bits of all DP-Slaves are off in 'Slave status area (Alarm detection)' (Un\G26416 to Un\G26420).
• Bits of all DP-Slaves are off in 'Slave status area (Diagnostic information detection)' (Un\G23056 to
Un\G23060).
If ACK is not returned for all alarms, BF LED turns off when bits of all DP-Slaves are off in 'Slave status area
(Diagnostic information detection)' (Un\G23056 to Un\G23060), regardless of the alarm detection status.
Summary of Contents for FX5-DP-M
Page 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Page 13: ...11 CONTENTS ...
Page 19: ...1 DESCRIPTION 17 1 MEMO ...
Page 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Page 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Page 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Page 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Page 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Page 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Page 175: ......