18
2 SPECIFICATIONS
2.1 General Specifications
2
SPECIFICATIONS
This section describes the specifications of FX5-DP-M.
2.1
General Specifications
General specifications other than the following are the same as the CPU module to be connected.
Refer to the following manual for general specifications.
MELSEC iQ-F FX5U User's Manual (Hardware)
MELSEC iQ-F FX5UC User's Manual (Hardware)
2.2
Power Supply Specifications
Shows power supply specifications.
2.3
Performance Specifications
Shows performance specifications of FX5-DP-M.
*1 Transmission speed accuracy is within
±
0.2% (compliant with IEC61158-2).
Item
Specifications
Dielectric withstand voltage
500 V AC for 1 minute
Between all terminals and frame of communication
connector
Insulation resistance
10 M
Ω
or higher with 500 V DC
insulation resistance tester
Item
Specifications
Internal power supply
Power-supply voltage
24 V DC
Current consumption
150 mA
Item
Description
PROFIBUS-DP station type
DP-Master (Class 1)
Transmis
sion
specifica
tions
Electrical standard and characteristics
Compliant with EIA-RS485
Medium
Shielded twisted pair cable (
Page 45 Wiring for PROFIBUS cable)
Network configuration
Bus topology (or tree topology when repeaters are used)
Data link method
• Between DP-Masters: Token passing
• Between DP-Master and DP-Slave: Polling
Encoding method
NRZ
Transmission speed
9.6 kbps, 19.2 kbps, 93.75 kbps, 187.5 kbps, 500 kbps, 1.5 Mbps, 3 Mbps, 6 Mbps, 12 Mbps
Transmission distance
Differs depending on the transmission speed. (
Page 19 Transmission distance)
Max. No. of repeaters (Between DP-Master and
DP-Slave)
3 repeaters
No. of connectable modules (per segment)
32 per segment (including repeaters)
Max. No. of DP-Slaves
64 (
Page 40 Configuration of PROFIBUS-DP network)
No. of connectable nodes (No. of repeaters)
32, 62(1), 92(2), 122(3), 126(4)
Transmittable data
Input data
Max. of 2048 bytes (Max. of 244 bytes per DP-Slave)
Output data
Max. of 2048 bytes (Max. of 244 bytes per DP-Slave)
No. of occupied I/O points
8 points
Applicable CPU module
FX5U CPU module (Ver.1.110 or later)
FX5UC CPU module (Ver.1.110 or later)
Applicable engineering tool
GX Works3 (Ver.1.050C or later )
PROFIBUS Configuration Tool (Ver.1.02C or later)
No. of connectable units
1 unit
Summary of Contents for FX5-DP-M
Page 1: ...MELSEC iQ F FX5 User s Manual PROFIBUS ...
Page 2: ......
Page 9: ...7 MEMO ...
Page 12: ...10 INDEX 168 REVISIONS 170 WARRANTY 171 TRADEMARKS 172 ...
Page 13: ...11 CONTENTS ...
Page 19: ...1 DESCRIPTION 17 1 MEMO ...
Page 100: ...98 9 PROGRAMMING 9 2 DP Master settings DP Slave FDL address 2 ...
Page 101: ...9 PROGRAMMING 9 2 DP Master settings 99 9 DP Slave FDL address 3 ...
Page 108: ...106 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 109: ...9 PROGRAMMING 9 8 Program Example of the Global Control Function 107 9 ...
Page 110: ...108 9 PROGRAMMING 9 8 Program Example of the Global Control Function ...
Page 112: ...110 9 PROGRAMMING 9 9 Program Example of Acyclic Communication Acyclic Communication ...
Page 114: ...112 9 PROGRAMMING 9 10 Program Example of the Alarm Acquisition Function ...
Page 169: ...APPX Appendix 4 Processing Time 167 A MEMO ...
Page 175: ......