253
4.20.7 Batch setting Mitsubishi HMI (GOT) connection parameters (Pr. 999)
The read value is always "9999."
....... Specifications differ according to the date assembled.
to check the SERIAL number.
(1) Automatic parameter setting
(Pr. 999)
Setting
Pr. 999
= "10" will automatically set the communication parameters required to connect a GOT to the PU
connector.
To operate in the parameter setting mode, go to "AUTO"
"GOT", then write "1".
The following tables show which parameters are changed in each of the automatic parameter settings.
GOT initial setting (PU connector) (
Pr. 999
= “10”)
Communication parameters for the Mitsubishi HMI (GOT) connection can be set as a batch.
Multiple parameters are changed automatically. Users do not have to consider each parameter number. (Parameter
setting mode)
Parameter
number
Name
Initial value
Setting range
Description
999
Automatic parameter
setting
9999
10
GOT initial setting (PU connector)
9999
No action
NOTE
If the automatic setting is performed with
Pr. 999
or the parameter setting mode, the listed settings including the changed
parameter settings (changed from the initial setting) will be automatically changed. Before performing the automatic setting,
confirm that changing the listed parameters will not cause any problem.
Parameter
number
Name
Initial
value
Automatically set to
Refer to Page
79
Operation mode selection
0
0
,
118
PU communication speed
192
192
,
119
PU communication stop bit length
1
10
,
120
PU communication parity check
2
1
,
121
Number of PU communication retries
1
9999
122
PU communication check time interval
0
9999
,
123
PU communication waiting time
9999
0ms
124
PU communication CR/LF selection
1
1
340
Communication startup mode selection
0
1
549
Protocol selection
0
0
,
REMARKS
Always perform a drive unit reset after the initial setting.