4.19.2 Regeneration avoidance function (Pr.665, Pr.882, Pr.883, Pr.885, Pr.886)
(1) What is regeneration avoidance function?
(Pr.882, Pr.883)
When the regeneration load is large, the DC bus voltage rises and an overvoltage fault (E. OV
) may occur. When this
bus voltage rise is detected and the bus voltage level reaches or exceeds
Pr.883
, increasing the speed avoids the
regeneration status.
The regeneration avoidance function is always ON when "1" is set in
Pr.882
and activated only during a constant speed
when "2" is set in
Pr.882
.
This function detects a regeneration status and increases the speed to avoid the regenerative status.
Possible to avoid regeneration by automatically increasing the speed and continue operation if the fan happens to
rotate faster than the set speed due to the effect of another fan in the same duct.
Parameter
number
Name
Initial
value
Setting
range
Description
882
Regeneration avoidance
operation selection
0
0
Regeneration avoidance function invalid
1
Regeneration avoidance function is always valid
2
Regeneration avoidance function is valid only during a
constant speed operation
883
Regeneration avoidance
operation level
400VDC
300 to 800V
Bus voltage level at which regeneration avoidance
operates. When he bus voltage level is set to low,
overvoltage error will be less apt to occur. However, the
actual deceleration time increases.
The set value must be higher than the "power supply
voltage
885
Regeneration avoidance
compensation speed limit
value
180r/min
0 to 540r/min
Limit value of speed which rises at activation of
regeneration avoidance function.
9999
Speed limit invalid
886
Regeneration avoidance
voltage gain
100%
0 to 200%
Responsiveness at activation of regeneration avoidance.
A larger setting will improve responsiveness to the bus
voltage change. However, the rotation speed could become
unstable.
When vibration is not suppressed by decreasing the
Pr.886
setting,
Pr.665
set a smaller value in
Pr.665
.
665
Regeneration avoidance
speed gain
100%
0 to 200%
The above parameters can be set when
Pr.160 Extended function display selection
= "0".
When an S-PM geared motor is used, the maximum setting value differs depending on the drive unit capacity. (0.2 to 2.2K: 1350 r/min, 3.7K: 900 r/min)
2
Pr.883
During regeneration
avoidance function operation
Time
Time
Bus voltage
(VDC)
Rotation
speed
(r/min)
Regeneration avoidance operation example
for acceleration
Pr.883
During regeneration avoidance
function operation
Time
Time
Bus voltage
(VDC)
Rotation
speed
(r/min)
Regeneration avoidance operation example
for constant speed
Pr.883
During regeneration
avoidance function operation
Time
Time
Bus voltage
(VDC)
Rotation
speed
(r/min)
Regeneration avoidance
operation example for deceleration