241
Special operation and speed control
<Set point input calibration>
1. Apply the input voltage of 0% set point setting (e.g. 0V) across terminals 2-5.
2. Enter in
C2 (Pr.902)
the speed which should be output by the drive unit at the deviation of 0% (e.g. 0r/min).
3. In
C3 (Pr.902)
, set the voltage value at 0%.
4. Apply the voltage of 100% set point (e.g. 5V) across terminals 2-5.
5. Enter in Pr.125 the speed which should be output by the drive unit at the deviation of 100% (e.g. 3000r/min).
6. In
C4 (Pr.903)
, set the voltage value at 100%.
<Measured value calibration>
1. Apply the input current of 0% measured value (e.g. 4mA) across terminals 4-5.
2. Make calibration using
C6 (Pr.904)
.
3. Apply the input current of 100% measured value (e.g. 20mA) across terminals 4-5.
4. Make calibration using
C7 (Pr.905)
.
The results of the above calibration are as shown below:
REMARKS
The speed set in
C5 (Pr.904)
and
Pr.126
should be the same as set in
C2 (Pr.902)
and
Pr.125
.
NOTE
Under position control, PID control is invalid.
If the RH, RM, RL signal (multi-speed) or JOG signal (Jog operation2) (Jog operation) is entered with the X14 signal
ON, PID control is stopped and multi-speed or Jog operation started.
When
Pr.79 Operation mode selection
="6" (switchover mode), PID control is invalid.
Changing the terminal function using any of
Pr.178 to Pr.184, Pr.190 to Pr.192
may affect the other functions. Set
parameters after confirming the function of each terminal.
When PID control is selected, the minimum speed is the speed set in
Pr.902
and the maximum speed is the speed set
in
Pr.903
.
(
Pr.1 Maximum setting
and
Pr.2 Minimum setting
are also valid.)
The remote operation function is invalid during PID operation.
When the control is switched to PID control during normal
operation, the speed command value calculated by PID
operation using 0r/min as standard is used without the speed
during the operation.
Parameters referred to
Pr.59 Remote function selection
Pr.73 Analog input selection
Pr.79 Operation mode selection
Pr.178 to Pr.184 (input terminal function selection)
Pr.190 to Pr.192 (output terminal function selection)
C2(Pr.902) to C7(Pr.905) Speed setting voltage (current) bias/gain
100
0
0
5
(V)
(%)
[Set point setting]
100
0
0
20 (mA)
(%)
[Measured value]
4
3000
0
0
100 Deviation (%)
[Manipulated variable]
Manipulated
variable(r/min)
PID action
Speed
command
PID set point
Speed command
during normal operation
ON
Operation when control is switched to PID control
during normal operation
Normal
operation
PID operation
Normal
operation