127
Setting of acceleration/deceleration time and acceleration/deceleration pattern
(4) Faulty acceleration rate detection
(Pr.375)
When the acceleration rate of the motor rotation speed is increased, such as when the machine collides against a foreign
object, the drive unit can cause the acceleration rate error (E.OA) to trip. The rotation speed calculated inside the drive
unit is used as the motor rotation speed.
Set
Pr.375 Faulty acceleration rate detection level
much larger than the acceleration/deceleration slope. If the setting of
Pr.375 Faulty acceleration rate detection level
is lower than the acceleration/deceleration slope, the acceleration rate error
(E.OA) occurs even during normal operation.
If rapid acceleration/deceleration is set for normal operation and the acceleration rate error (E.OA) occurs, the
acceleration rate error detection cannot be used. Set
Pr.375
= "9999" to disable the acceleration rate error detection.
(5) Setting the acceleration/deceleration time in the low-speed range
(Pr.791, Pr.792 )
If torque is required in a low-speed range at 300 r/min or lower (600 r/min or lower for driving MM-GKR13), set
Pr.791
Acceleration time in low-speed range
and
Pr.792 Deceleration time in low-speed range
settings higher than the
Pr.7 Acceleration
time
and
Pr.8 Deceleration time
settings so that the mild acceleration/deceleration is performed only in the low-speed
range.
If torque is required in the low-speed range (600r/min or less), set
Pr.791 Acceleration time in low-speed range
and
Pr.792
Deceleration time in low-speed range
settings higher than the
Pr.7 Acceleration time
and
Pr.8 Deceleration time
settings so that
the mild acceleration/deceleration is performed in the low-speed range.
Set the time for the acceleration from a stop to
Pr.20 Acceleration/deceleration reference speed
as the acceleration time. Set
the time for the deceleration from
Pr.20 Acceleration/deceleration reference speed
to a stop as the deceleration time.
REMARKS
The RT signal acts as the second function selection signal and makes the other second function valid.
)
If the
Pr.20
setting is changed, the
Pr.125
and
Pr.126 (speed setting signal gain speed)
settings do not change. Set
Pr.125
and
Pr.126
to adjust the gains.
Set
Pr.791
higher than
Pr.7
, and
Pr.792
higher than
Pr.8
. If set as
Pr.791
<
Pr.7
, the operation is performed as
Pr.791
=
Pr.7
. If set
as
Pr.792
<
Pr.8
, the operation is performed as
Pr.792
=
Pr.8
.
If the acceleration/deceleration time is set, the actual motor acceleration/deceleration time cannot be made shorter than the
shortest acceleration/deceleration time determined by the mechanical system J (moment of inertia) and motor torque.
Rotation speed
(r/min)
Acceleration rate
(r/min/ms)
Fault output
0
Time
0
Speed command
Rotation speed
Time
E.OA
E.OA
Pr.375
Pr.375
E.OA
Low-speed range
Acceleration time
Slope set by
Pr.7
Deceleration time
Slope set by
Pr.8
Deceleration time
in low-speed range
Slope set by
Pr.792
Acceleration time
in low-speed range
Slope set by
Pr.791
Time
Rotation
speed (r/min)
Summary of Contents for FR-E700EX
Page 11: ...VII MEMO ...
Page 23: ...12 MEMO ...
Page 288: ...286 MEMO ...
Page 302: ...300 MEMO ...
Page 314: ...312 MEMO ...