233
Communication operation and setting
Faults history
Fault code list
Model information monitor
(7)
Pr.343
Communication error count
You can check the cumulative number of communication errors.
(8) Output terminal LF "alarm output (communication error warnings)"
During a communication error, the alarm signal (LF signal) is output by open collector output. Assign the used terminal
using any of
Pr.190 to Pr.192 (output terminal function selection)
.
Register
Definition
Read/Write
Remarks
40501
Fault history 1
Read/Write
Being 2 bytes in length, the data is stored as "H00
".
Refer to the lowest 1 byte for the error code.
Performing write using the register 40501 batch-clears
the faults history.
Set any value as data.
40502
Fault history 2
Read
40503
Fault history 3
Read
40504
Fault history 4
Read
40505
Fault history 5
Read
40506
Fault history 6
Read
40507
Fault history 7
Read
40508
Fault history 8
Read
Register
Definition
Read/Write
Remarks
44001 to 44010
Drive unit
model
Read
Reading drive unit model in ASCII code.
"H20" (blank code) is set for blank area
Example of FR-E720EX
H46, H52, H2D, H45, H37, H32, H30, H45, H58, H20 ......H20
44011 to 44013
Capacity
Read
Reading drive unit capacity in ASCII code.
Data is read in increments of 0.1kW, and rounds down to
0.01kW increments
"H20" (blank code) is set for blank area
Example
0.75K................" 7" (H20, H20, H20, H20, H20, H37)
Parameter
Setting Range
Minimum Setting Range
Initial Value
343
(Reading only)
1
0
NOTE
The number of communication errors is temporarily stored into the RAM. As it is not stored into the EEPROM
performing a power supply reset or drive unit reset clears the value to 0.
NOTE
The LF signal can be assigned to the output terminal using any of
Pr.190 to Pr.192
. Changing the terminal assignment
may affect the other functions. Set parameters after confirming the function of each terminal.
for details of fault description.
Data
Definition
H00
No fault
present
H10
E.OC1
H11
E.OC2
H12
E.OC3
H20
E.OV1
H21
E.OV2
H22
E.OV3
H30
E.THT
H31
E.THM
H40
E.FIN
H52
E.ILF
H60
E.OLT
H61
E.SOT
H70
E.BE
H80
E.GF
H81
E.LF
H90
E.OHT
HA0
E.OPT
HA1
E.OP1
Data
Definition
HB0
E.PE
HB1
E.PUE
HB2
E.RET
HB3
E.PE2
HC0
E.CPU
HC5
E.IOH
HC7
E.AIE
HC8
E.USB
HC9
E.SAF
HD0
E.OS
Data
Definition
HD1
E.OSD
HD3
E.OD
HDD
E.OA
HF1
E.1
HF5
E.5
HF6
E.6
HF7
E.7
HFD
E.13
Data
Definition
Alarm data
Reply data
Master
Slave
Communication
Error count
(Pr.343)
0
LF signal
Normal data
Alarm data
Alarm data
Normal data
Reply data
1
2
OFF
ON
OFF
OFF
ON
Not increased
Communication error count is increased
in synchronization with leading edge
of LF signal
Turns OFF when normal data is received
Alarm data: Data resulting in communication error.