Setting from the parameter unit and operation panel
(3) Disable the setting dial and key operation of the operation panel (Press [MODE] long (2s))
Operation using the setting dial and key of the operation panel can be invalid to prevent parameter change, and
unexpected start or speed setting.
Set "10 or 11" in
Pr.161
, then press
for 2s to make the setting dial and key operation invalid.
When the setting dial and key operation are invalid,
appears on the operation panel. If dial or key operation
is attempted while dial and key operation are invalid,
appears. (When dial or key is not touched for 2s,
monitor display appears.)
To make the setting dial and key operation valid again, press
for 2s.
REMARKS
Even if the setting dial and key operation are disabled, the monitor display and
are valid.
NOTE
Release the operation lock to release the PU stop by key operation.
When setting speed by turning the setting dial, the speed goes up to the set value of
Pr.1 Maximum setting
(initial value:
3000r/min). Adjust
Pr.1 Maximum setting
according to the application.