Function assignment of external terminal and control
4.12.5 Output terminal function selection (Pr.190 to Pr.192)
(1) Output signal list
You can set the functions of the output terminals.
Refer to the following table and set the parameters: (0 to 99: positive logic, 100 to 199: negative logic)
You can change the functions of the open collector output terminal and relay output terminal.
Parameter
number
Name
Initial
value
Initial signal
Setting range
190
RUN terminal function
selection
Open
collector
output
terminal
0
RUN (drive unit
runnning)
0, 1, 3, 4, 7, 8, 11 to 16, 21,
24 to 26, 33, 36, 38, 47, 55, 56,
60, 61, 63, 64, 68
95, 96, 98, 99, 100, 101, 103,
104, 107, 108, 111 to 116, 121,
124 to 126, 133, 136, 138, 147,
155, 156, 160, 161, 163, 164,
168
, 190, 191, 193
, 195, 196,
198, 199, 9999
191
FU terminal function
selection
4
FU (rotation speed
detection)
192
A,B,C terminal function
selection
Relay
output
terminal
99
ALM (fault output)
The above parameters can be set when
Pr.160 Extended function display selection
= "0".
The setting values "93" and "193" are available only in
Pr.190 and Pr.191
.
The setting values "68" and "168" are valid only when used with FR-E7DS. (For the details, refer to the Instruction Manual of FR-E7DS.)
...... Specifications differ according to the date assembled.
to check the SERIAL number.
Setting
Signal
Function
Operation
Related
parameter
Refer
to
page
Positive
logic
Negative
logic
0
100
RUN
Drive unit running
Speed
control
Output when the drive unit starts running
upon turning ON of the start signal.
Turned OFF when the drive unit performs
deceleration stop and zero speed control
or servo lock is activated.
Position
control
Same operation as that of the RY2 signal
1
101
SU
Up to speed
Speed
control
Output when the rotation speed is reached
to the set speed.
Pr.41, Pr.870
Position
control
3
103
OL
Overload alarm
Output while torque limit function is activated.
Pr.22, Pr.48,
Pr.156, Pr.157
4
104
FU
Rotation speed detection
Output when the rotation speed reaches the speed
set in
Pr.42
(
Pr.43
for reverse rotation).
Pr.42, Pr.43,
Pr.870
7
107
RBP
Regenerative brake pre-
alarm
Output when 85% of the regenerative brake duty set
in
Pr.70
is reached.
Pr.70
8
108
THP
Electronic thermal O/L
relay pre-alarm
Output when the electronic thermal value reaches
85% of the trip level. (Electronic thermal relay
function protection (E.THT/E.THM) activates, when
the value reached 100%.)
Pr.9
11
111
RY
Drive unit operation ready
Output when reset process is completed (when the
drive unit can be started by switching the start signal
ON or while it is running) after power-ON of the drive
unit.
12
112
Y12
Output current detection
Output when the output current is the
Pr.150
setting or
higher for longer than the time set in
Pr.151
.
Pr.150, Pr.151
13
113
Y13
Zero current detection
Output when the output power is the
Pr.152
setting or
lower for longer than the time set in
Pr.153
.
Pr.152, Pr.153