INSTALLATION AND WIRING
14
"
"
"
"
Single-phase 200V power input
Power supply
NFB
L
1
N
Motor
IM
Earth(Ground)
U
V
W
MC
Note: 1. To ensure safety, connect the power input to the inverter via a magnetic
contactor and earth leakage circuit breaker or no-fuse breaker, and use the
magnetic contactor to switch power on-off.
2. The output is three-phase 200V.
(1) Description of the main circuit terminals
Symbol
Terminal Name
Description
L
1
, L
2
, L
3
(Note)
AC power input
Connect to the commercial power supply.
Keep these terminals unconnected when using the high
power factor converter.
U, V, W
Inverter output
Connect a three-phase squirrel-cage motor.
+, PR
Brake resistor
connection
Connect the optional brake resistor across ter -
PR.
+,
−
Brake unit
connection
Connect the optional brake unit or high power factor
converter.
+, P1
Power factor
improving DC
reactor connection
Disconnect the jumper from ter - P1 and connect
the optional power factor improving DC reactor.
Earth (Ground)
For earthing the inverter chassis. Must be earthed.
Note: L
1
, N terminals for single-phase power input.
2