PARAMETERS
156
<Operation procedure>
!
When using the control panel (FR-PA02-
02
)
1) Select the PU operation mode.
4) Read Pr. 901 "AM terminal calibration".
2) Set the running frequency.
6) Hold down the / key to adjust the meter pointer to a required position.
(Depending on the setting, it may take some time until the pointer moves.)
3) Press the key.
SET
5) Press the key to run the inverter. (Motor need not be connected.)
FWD
8) Press the key to stop the inverter.
STOP
RESET
7) Press the key for about 1.5 s.
SET
REMARKS
Calibration can also be made for external operation. Set the frequency in the external
operation mode and make calibration in the steps 4) to 8).
Note:
It is possible to calibrate even during operation.