PARAMETERS
150
"
Output terminal function selection (Pr. 190 to Pr. 192)
4.2.44 Output terminal function selection (Pr. 190 to Pr. 192)
Pr. 190 "RUN terminal function selection"
Pr. 191 "FU terminal function selection"
Pr. 192 "A, B, C terminal function selection"
You can change the functions of the open collector and contact output terminals.
Parameter
Number
Terminal
Symbol
Factory
Setting
Factory-Set Terminal
Function
Setting
Range
190
RUN
0
Inverter running
0 to 99
191
FU
4
Output frequency detection
0 to 99
192
ABC
99
Alarm output
0 to 99
<Setting>
Refer to the following table and set the parameters:
Setting
Signal
Name
Function
Operation
Related
Parameters
0
RUN
Inverter running
Output during operation when
the inverter output frequency
rises to or above the starting
frequency.
1
SU
Up to frequency
Refer to Pr. 41 "up-to-frequency
sensitivity". (Note 1)
Pr. 41
3
OL
Overload alarm
Output while stall prevention
function is activated.
Pr. 22, Pr. 23,
Pr. 66
4
FU
Output frequency
detection
Refer to Pr. 42, Pr. 43 (output
frequency detection).
Pr. 42, Pr. 43
11
RY
Inverter operation
ready
Output when the inverter is
ready to be started by switching
the start signal on.
12
Y12
Output current
detection
Refer to Pr. 150 and Pr. 151
(output current detection).
Pr. 150,
Pr. 151
13
Y13
Zero current
detection
Refer to Pr. 152 and Pr. 153
(zero current detection).
Pr. 152,
Pr. 153
14
FDN
PID lower limit
15
FUP
PID upper limit
16
RL
PID forward-
reverse rotation
output
Refer to Pr. 128 to Pr. 134 (PID
control).
Pr. 128 to
Pr. 134
98
LF
Minor fault output
Output when a minor fault (fan
failure or communication error
warning) occurs.
Pr. 121,
Pr. 244
99
ABC
Alarm output
Output when the inverter's
protective function is activated to
stop the output (major fault).
Note: 1. The same function may be set to more than one terminal.
2. Pr. 190 to Pr. 192 do not function if the values set are other than the above.