PARAMETERS
138
(4) I/O signals
Signal
Terminal Used
Function
Description
2
2
Set point input
Enter the set point for PID control.
Input
4
4
Process value input
Enter the 4 to 20mADC process value signal
from the detector.
FUP
Upper limit output
Output to indicate that the process value
signal exceeded the upper limit value.
FDN
Lower limit output
Output to indicate that the process value
signal exceeded the lower limit value.
Ou
tp
u
t
RL
Depending on
Pr. 190 to
Pr. 192
Forward (reverse)
rotation direction
output
"Hi" is output to indicate that the output
indication of the parameter unit is forward
rotation (FWD) or "Low" to indicate that it is
reverse rotation (REV) or stop (STOP).
"
"
"
"
Enter the set point across inverter terminals 2-5 or in Pr. 133 and enter the process
value signal across inverter terminals 4-5. At this time, set "20" or "21" in Pr. 128.
Item
Entry
Description
Set 0V as 0% and
5V as 100%.
When "0" or "10" is set in Pr. 73
(5V selected for terminal 2).
Across terminals 2-5
Set 0V as 0% and
10V as 100%.
When "1" or "11" is set in Pr. 73
(10V selected for terminal 2).
Set point
Pr. 133
Set the set point (%) in Pr. 133.
Process value
Across terminals 4-5 4mA DC is equivalent to 0% and 20mA DC to 100%.