PARAMETERS
119
<Link start mode>
The operation mode at power on and at restoration from instantaneous power failure
can be selected.
To choose the NET mode communication, set "1" in Pr. 340.
Pr. 340
Setting
Pr. 79
Operation Mode
Mode at Power On or at Restoration
from Instantaneous Power Failure
0
PU or external
operation
Inverter goes into the external operation mode.
1
PU operation
Inverter goes into the PU operation mode.
2
External operation
Inverter goes into the external operation mode.
3
External/PU
combined operation
mode
Running frequency is set in the PU operation
mode and the start signal is set in the external
operation mode.
4
External/PU
combined operation
mode
Running frequency is set in the external operation
mode and the start signal is set in the PU
operation mode.
6
Switch-over mode
Operation mode is switched while running.
7
External operation
mode
MRS signal ON ....Shift to the PU operation mode
enabled (output stopped during
external operation)
MRS signal OFF ..Shift to the PU operation mode
inhibited
0
(Factory
Setting)
8
External/PU
combined operation
mode
X16 signal ON .....Shift to external operation mode
X16 signal OFF....Shift to PU operation mode
1
NET mode communication
Inverter goes into the NET mode communication
mode. (Program need not be used for switching)
1) The Pr. 340 value may be changed in any operation mode.
2) When Pr. 79 "operation mode selection" = "0, 2 or 6", "1" in Pr. 340 is made valid.
4