PARAMETERS
65
Func-
tion
Para-
meter
Number
Name
Setting
Range
Minimum
Setting
Increments
Factory
Setting
Refer
To:
Custo-
mer
Setting
St
op
sel
e
ct
io
n
funct
ion
250
Stop selection
0 to 100 s,
1000 to
1100 s,
8888, 9999
1
9999
153
251
Output phase failure
protection selection
0, 1
1
1
154
Addit
ional
funct
ion
254
analog polarity reversible
lower limit (Note 11)
0 to 100%,
9999
0.1%
9999
100
338
Operation command right
(Note 12)
0, 1
1
0
117
339
Speed command right (Note
12)
0, 1
1
0
117
340
Link start mode selection
(Note 12)
0, 1
1
0
117
Com
put
er link
funct
ion
342
E
2
PROM write selection
0, 1
1
0
117
901
AM terminal calibration
155
902
Frequency setting voltage
bias
0 to
10V
0 to
60Hz
0.01Hz
0V 0Hz
157
903
Frequency setting voltage
gain
0 to
10V
1 to
400
Hz
0.01Hz
5V
50
Hz
157
904
Frequency setting current
bias
0 to
20
mA
0 to
60Hz
0.01Hz
4
mA
0Hz
157
905
Frequency setting current
gain
0 to
20
mA
1 to
400
Hz
0.01Hz
20
mA
50
Hz
157
990
Calibrat
ion f
unct
ions
991
Parameter for option (FR-PU04).
Note: 1. Indicates the parameter of which setting is ignored when the general-
purpose magnetic flux vector control mode is selected.
2. Since calibration is made before shipment from the factory, the settings differ
slightly between inverters. The inverter is preset to provide a frequency
slightly higher than 50Hz.
3. When the control panel is used and the setting is 100Hz or more, the setting
increments are 0.1Hz.
The setting increments are 0.01Hz when the communication mode.
4. The setting depends on the inverter capacity: (0.4K to 3.7K)/(5.5K to 7.5K).
5. Set to 85% of the rated inverter current for the 0.4K, 0.75K.
6. If "2" is set in Pr. 77 (parameter write inhibit selection), the setting cannot be
changed during operation.
7. The half-tone screened parameters allow their settings to be changed during
operation if "0" (factory setting) has been set in Pr. 77 (parameter write
inhibit selection). (However, the Pr. 72 and Pr. 240 values may be changed
during PU operation only.)
8. The setting depends on the inverter capacity: 4% for the FR-E540-5.5K and
7.5K-EC.
9. To set "10" or "11" in Pr. 73, first "801" must set in Pr. 77.
10. For the FR-E540-5.5K and 7.5K-EC, the factory setting is 10s.
11. When setting Pr. 254, set "801" in Pr. 77.
12. Pr. 338 to Pr. 340 are displayed only when the communication option is fitted
or when Pr. 119 is "100, 101, 110 or 111".
4
Parameter L
ist