232
(1) Life alarm display and signal output (Y90 signal,
Pr. 255
)
Whether any of the control circuit capacitor, main circuit capacitor, cooling fan and inrush current limit circuit has reached
the life alarm output level or not can be checked by
Pr. 255 Life alarm status display
and Life alarm (Y90) signal.
The Life alarm (Y90) signal turns ON when any of the control circuit capacitor, main circuit capacitor, cooling fan and
inrush current limit circuit reaches the life alarm output level.
For the terminal used for the Y90 signal, set "90" (positive logic) or "190" (negative logic) to
Pr. 190
or
Pr. 192 (output
terminal function selection)
.
(2) Inrush current limit circuit life display
(Pr. 256)
The life of the inrush current limit circuit (relay, contactor and inrush resistor) is displayed in
Pr. 256
.
Activation of inrush current limit resistor circuit is counted. It is counted every 10,000 times (1%) and counts down from
100% (0 time).
As soon as 10% (900,000 times) is reached,
Pr. 255
bit 3 is turned ON and also an alarm is output to the Y90 signal.
The inrush current limit resistor circuit activates under the following conditions:
At power-ON
At undervoltage occurrence
At drive unit reset
(3) Control circuit capacitor life display
(Pr. 257)
The deterioration degree of the control circuit capacitor is displayed in
Pr. 257
as a life.
In the operating status, the control circuit capacitor life is calculated from the energization time and temperature, and is
counted down from 100%.
As soon as the control circuit capacitor life falls below 10%,
Pr. 255
bit 0 is turned ON and also an alarm is output to the
Y90 signal.
Pr. 255
(decimal)
Bit
(binary)
Inrush Current
Suppression
Circuit Life
Cooling
Fan Life
Main Circuit
Capacitor Life
Control Circuit
Capacitor Life
15
1111
14
1110
13
1101
12
1100
11
1011
10
1010
9
1001
8
1000
7
0111
6
0110
5
0101
4
0100
3
0011
2
0010
1
0001
0
0000
: With warnings,
: Without warnings
NOTE
Changing the terminal assignment using
Pr. 190
and
Pr. 192 (output terminal function selection)
may affect the other
functions. Set parameters after confirming the function of each terminal.
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0
bit0 Control circuit capacitor life
1
15
bit
7
0
bit1 Main circuit capacitor life
bit2 Cooling fan life
bit3 Inrush current limit circuit life
Pr. 255
read
Pr. 255
setting read
Bit image is displayed
in decimal