188
Communication operation and setting
(3) Stop operation selection at occurrence of communication fault
(Pr. 502)
Stop operation when retry count exceeds (Mitsubishi inverter protocol only) or signal loss detection error occurs can be
selected.
Operation at fault occurrence
Operation at fault removal
Pr. 502
Setting
Operation
Indication
Fault Output
0 (initial value)
Coasts to stop
E. PUE lit
Provided
1
Decelerates to stop
E. PUE lit after stop
Provided after stop
2
Not provided
3
Operates at the speed set in
Pr. 779
Normal display
Not provided
Pr. 502
Setting
Operation
Indication
Fault Output
0 (initial value)
Kept stopped
E. PUE
Kept provided
1
2
Automatic restart functions
Normal display
Not provided
3
Normal operation
Normal display
Not provided
Pr. 502
setting = "0" (initial value)
Pr. 502
setting = "1"
Pr. 502
setting = "2"
Pr. 502
setting = "3"
When a communication error is detected while
Pr. 502
= "3," the alarm (LF) is output to an output terminal of the drive unit. To use the LF signal, assign the
function to an output terminal by setting "98 (positive logic) or 198 (negative logic)" in
Pr. 190
or
Pr. 192 (Output terminal function selection)
.
Time
Communication
fault
Rotation speed
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
ON
OFF
Motor coasting
Fault occurrence
Fault removal
Time
Communication
fault
Rotation speed
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
ON
OFF
Decelerates to stop
Fault occurrence
Fault removal
Time
Communication
fault
Rotation speed
Fault display
(E.PUE)
Fault output
(ALM)
ON
OFF
OFF
Display
OFF
Decelerates
to stop
Fault occurrence
Fault removal
Time
Communication
fault
Fault display
Fault output
(ALM)
ON
OFF
OFF
OFF
OFF
OFF
Fault recognition
Fault removal
Pr. 779
= "9999"
Not displayed
Rotation speed
ON
Alarm output
(LF)
∗
Pr. 779
"9999"
(Runs at the speed setting of
Pr. 779 )