141
Monitor display and monitor output signal
4.12.5 How to calibrate the terminal FM when using the operation panel
Follow the following procedure to calibrate terminal FM using the operation panel.
Refer to
page 140
for the details of parameters.
Operation Display
1.
Confirm the operation status indicator and
operation mode indicator
(When
Pr. 54
= 1)
2.
Press
to choose the parameter setting
mode.
PRM indicator is lit.
(The parameter number read previously appears.)
3.
Turn
until "
" appears.
4.
Press
to read the present set value.
"
" (initial value) appears.
5.
Turn
to change it to the setting value of
" ".
6.
Press
to set.
Blink...Parameter setting complete!!
7.
Turn
until "
" appears.
8.
Press
to display "
".
9.
Turn
until "
" appears.
Set to
C0 FM terminal calibration.
10.
Press
to enable setting.
11.
If the drive unit is at a stop, press the
key to start the drive unit.
When a monitor that does not require the drive
unit operation is set in
Pr. 54
, calibration is also
possible during a stop status.
12.
Turn
to adjust the indicator needle to
the desired position.
Analog indicator
13.
Press
.
Setting is complete.
Blink...Parameter setting complete!!
Turn
to read another parameter.
Press
to return to the "
" indication (step 4).
Press
twice to show the next parameter ("
").
C1 to C7 setting
is enabled.
The monitor set to
Pr. 54
FM terminal function selection
is displayed.
Hz
A