11
Drive unit placement
1.5 Drive unit placement
Enclosure surface mounting
Remove the front cover and wiring cover to mount the drive unit to the surface. (Remove the covers in the directions of the
arrows.)
NOTE
When encasing multiple drive units, install them in parallel as a
cooling measure.
Install the drive unit vertically.
For heat dissipation and maintenance, allow minimum clearance
shown in the figures below from the drive unit to the other devices
and to the inner surface of the enclosure.
* When using the drive units at the surrounding air temperature of 40
C or less, the drive units can be installed without any clearance between
them (0cm clearance).
When designing or building an enclosure for the drive unit, carefully consider influencing factors such as heat
generation of the contained devices and the operating environment.
Front cover
Front cover
Wiring cover
Wiring cover
FR-D720-0.2K to 0.75K-G
FR-D720-1.5K to 3.7K-G
FR-D740-0.4K to 3.7K-G
V
ertical
Refer to the clearance
shown on the left.
10cm or more
10cm or more
Measurement
position
Measurement
position
5cm
5cm
5cm
-10 C to
+
50 C
(non-freezing)
1cm or
more
∗
1cm or
more
∗
1cm or
more