WIRING
*1
No input voltage is allowed for these terminals.The function of these terminals can be changed with the input terminal assignment
(Pr. 178 to Pr. 189). (Refer to
.)
*2
Terminal JOG is also used as the pulse train input terminal. Use Pr. 291 to choose JOG or pulse.
*3
Terminal input specifications can be changed by analog input specification switchover (Pr. 73, Pr. 267). To input a voltage (0 to 5 V/0 to
10 V), set the voltage/current input switch OFF. To input a current (4 to 20 mA), set the voltage/current input switch ON. Terminals 10
and 2 are also used as a PTC input terminal. (Pr. 561) (Refer to the FR-A800 Instruction Manual.)
*4
It is recommended to use 2W, 1k
Ω
when the frequency setting signal is changed frequently.
*5
The function of these terminals can be changed with the output terminal assignment (Pr. 195, Pr. 196). (Refer to
*6
The function of these terminals can be changed with the output terminal assignment (Pr. 190 to Pr. 194). (Refer to
*7
The terminal F/C (FM) can be used to output pulse trains as open collector output by setting Pr. 291.
*8
Not required when calibrating the scale with the operation panel.
CAUTION
To prevent a malfunction due to noise, keep the signal cables more than 10cm away from the power cables. Also, separate the main
circuit cables at the input side from the main circuit cables at the output side.
After wiring, wire offcuts must not be left in the inverter.
Wire offcuts can cause an alarm, failure or malfunction. Always keep the inverter clean.
When drilling mounting holes in a control box etc., take care not to allow chips and other foreign matter to enter the inverter.
Set the voltage/current input switch in the correct position. An incorrect setting may cause a fault, failure or malfunction.