43
DRIVE THE MOTOR
753
Second PID action
selection
0, 10, 11, 20, 21,
50, 51, 60, 61,
70, 71, 80, 81,
90, 91, 100,
101, 1000,
1001, 1010,
1011, 2000,
2001, 2010,
2011
0
754
Second PID control
automatic switch-
over frequency
0 to 590Hz,
9999
9999
755
Second PID action
set point
0 to 100%,
9999
9999
756
Second PID
proportional band
0.1 to 1000%,
9999
100 %
757
Second PID integral
time
0.1 to 3600s,
9999
1 s
758
Second PID
differential time
0.01 to 10.00s,
9999
9999
759
PID unit selection
0 to 43,
9999
9999
760
Pre-charge fault
selection
0, 1
0
761
Pre-charge ending
level
0 to 100%,
9999
9999
762
Pre-charge ending
time
0 to 3600s,
9999
9999
763
Pre-charge upper
detection level
0 to 100%,
9999
9999
764
Pre-charge time limit
0 to 3600s,
9999
9999
765
Second pre-charge
fault selection
0, 1
0 %
766
Second pre-charge
ending level
0 to 100%,
9999
9999
767
Second pre-charge
ending time
0 to 3600s,
9999
9999
768
Second pre-charge
upper detection level
0 to 100%,
9999
9999
769
Second pre-charge
time limit
0 to 3600s,
9999
9999
774
Operation panel
monitor selection 1
1 to 3, 5 to 14,
17 to 20, 22 to
35, 38, 40 to 45,
50 to 57, 61, 62,
64, 67, 87 to 98,
100, 9999
9999
775
Operation panel
monitor selection 2
9999
776
Operation panel
monitor selection 3
9999
777
4mA input fault
operation frequency
0 to 590Hz,
9999
9999
778
4mA input check
filter
0 to 10s
0
Parameter Name
Setting Range
Initial
Value
779
Operation frequency
during
communication error
0 to 590Hz,
9999
9999
788
Low speed range
torque characteristic
selection
0, 9999
9999
791
Acceleration time in
low-speed range
0 to 3600s,
9999
9999
792
Deceleration time in
low-speed range
0 to 3600s,
9999
9999
799
Pulse increment
setting for output
power
0.1, 1, 10, 100,
1000kWh
1kWh
800
Control method
selection
0 to 6, 9 to 14,
20, 100 to 106,
109 to 114
20
802
Pre-excitation
selection
0, 1
0
803
Constant output
range torque
characteristic
selection
0, 1, 10, 11
0
804
Torque command
source selection
0, 1, 3 to 6
0
805
Torque command
value (RAM)
600 to 1400%
1000%
806
Torque command
value (RAM,
EEPROM)
600 to 1400%
1000%
807
Speed limit selection
0 to 2
0
808
Forward rotation
speed limit/speed
limit
0 to 400Hz
60/50Hz
*10
809
Reverse rotation
speed limit/reverse-
side speed limit
0 to 400Hz,
9999
9999
810
Torque limit input
method selection
0, 1
0
811
Set resolution
switchover
0, 1, 10, 11
0
812
Torque limit level
(regeneration)
0 to 400%, 9999
9999
813
Torque limit level
(3rd quadrant)
0 to 400%, 9999
9999
814
Torque limit level
(4th quadrant)
0 to 400%, 9999
9999
815
Torque limit level 2
0 to 400%, 9999
9999
816
Torque limit level
during acceleration
0 to 400%, 9999
9999
Parameter Name
Setting Range
Initial
Value
*10
Differs according to types. (FM type/CA type)
Summary of Contents for FR-A800