36
DRIVE THE MOTOR
141
Backlash
acceleration
stopping time
0 to 360s
0.5s
142
Backlash
deceleration
stopping frequency
0 to 590Hz
1Hz
143
Backlash
deceleration
stopping time
0 to 360s
0.5s
144
Speed setting
switchover
0, 2, 4, 6, 8, 10,
102, 104, 106,
108, 110, 112
4
145
PU display language
selection
0 to 7
1
147
Acceleration/
deceleration time
switching frequency
0 to 590Hz,
9999
9999
148
Stall prevention level
at 0V input
0 to 400%
150%
149
Stall prevention level
at 10V input
0 to 400%
200%
150
Output current
detection level
0 to 400%
150%
151
Output current
detection signal
delay time
0 to 10s
0s
152
Zero current
detection level
0 to 400%
5%
153
Zero current
detection time
0 to 10s
0.5s
154
Voltage reduction
selection during stall
prevention operation
0, 1, 10, 11
1
155
RT signal function
validity condition
selection
0, 10
0
156
Stall prevention
operation selection
0 to 31, 100,
101
0
157
OL signal output
timer
0 to 25s, 9999
0s
158
AM terminal function
selection
1 to 3, 5 to 14,
17, 18, 21, 24,
32 to 34, 50, 52
to 54, 61, 62,
67, 70, 87 to 90,
91 to 98
1
159
Automatic switch-
over frequency range
from bypass to
inverter operation
0 to 10Hz, 9999
9999
160
User group read
selection
0, 1, 9999
0
161
Frequency setting/
key lock operation
selection
0, 1, 10, 11
0
162
Automatic restart
after instantaneous
power failure
selection
0 to 3, 10 to 13
0
163
First cushion time for
restart
0 to 20s
0s
164
First cushion voltage
for restart
0 to 100%
0%
Parameter Name
Setting Range
Initial
Value
Simple
Simple
Simple
165
Stall prevention
operation level for
restart
0 to 400%
150%
166
Output current
detection signal
retention time
0 to 10s, 9999
0.1s
167
Output current
detection operation
selection
0, 1, 10, 11
0
168
Parameter for manufacturer setting.
Do not make setting.
169
170
Watt-hour meter
clear
0, 10, 9999
9999
171
Operation hour
meter clear
0, 9999
9999
172
User group
registered display/
batch clear
9999, (0 to 16)
0
173
User group
registration
0 to 1999, 9999
9999
174
User group clear
0 to 1999, 9999
9999
178
STF terminal
function selection
0 to 20, 22 to
28, 37, 42 to 47,
50, 51, 60 to 62,
64 to 74, 76 to
80, 87, 92, 93,
9999
*12
60
179
STR terminal
function selection
61
180
RL terminal function
selection
0
181
RM terminal function
selection
1
182
RH terminal function
selection
2
183
RT terminal function
selection
3
184
AU terminal function
selection
4
185
JOG terminal
function selection
5
186
CS terminal function
selection
6
187
MRS terminal
function selection
24/10/24
*
15
188
STOP terminal
function selection
25
189
RES terminal
function selection
62
190
RUN terminal
function selection
0 to 8, 10 to 20,
22, 25 to 28, 30
to 36, 38 to 54,
56, 57, 60, 61,
63, 64, 68, 70,
79, 84, 85, 90 to
99, 100 to 108,
110 to 116, 120,
122, 125 to 128,
130 to 136, 138
to 154, 156,
157, 160, 161,
163, 164, 168,
170, 179, 184,
185, 190 to 199,
200 to 208, 300
to 308, 9999
*13
0
191
SU terminal function
selection
1
192
IPF terminal function
selection
2/9999/2
*
15
193
OL terminal function
selection
3
194
FU terminal function
selection
4
195
ABC1 terminal
function selection
99
196
ABC2 terminal
function selection
9999
Parameter Name
Setting Range
Initial
Value
*12
The setting value "60" is only available for Pr. 178, and "61" is only for Pr. 179.
*13
The setting values "92, 93, 192, 193" are only available for Pr. 190 to Pr. 194.
*15
Differs according to model types (standard model, separated converter type, IP55 compatible model).
Summary of Contents for FR-A800
Page 67: ......