Wiring protection
For installation Class T, Class J, or Class CC fuse or UL 489 Molded Case Circuit Breaker (MCCB) according to the local
directives must be provided.
*1
Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
For wiring protection of the converter unit (FR-CC2) refer to the FR-CC2 Instruction Manual-
A.1.3 Short circuit ratings
200V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 264V maximum.
400V class
Suitable for use in a circuit capable of delivering not more than 100kA rms symmetrical amperes, 550V or 600V
maximum.
A.1.4 Machinery directive
The frequency inverter itself is not a machine in the spirit of the EU machinery directive. The start up of the frequency
inverter in a machine is prohibited so long until it has been confirmed that the entire machine complies with the provisions
of Directive 98/37/EC (from 29.12.2009 Machinery Directive 2006/42/EC).
FR-A820-
00046
(0.4K)
00077
(0.75K)
00105
(1.5K)
00167
(2.2K)
00250
(3.7K)
00340
(5.5K)
00490
(7.5K)
00630
(11K)
00770
(15K)
00930
(18.5K)
01250
(22K)
01540
(30K)
Rated fuse voltage [V]
240V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
15
20
30
40
60
80
150
175
200
225
300
350
With power factor
improving reactor
15
20
20
30
50
70
125
150
200
200
250
300
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15
15
25
40
60
80
110
150
190
225
300
350
FR-A820-
01870
(37K)
02330
(45K)
03160
(55K)
03800
(75K)
04750
(90K)
Rated fuse voltage [V]
240V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
400
500
500
—
—
With power factor
improving reactor
350
400
500
600
700
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
450
500
700
900
1000
FR-A840-
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
00620
(22K)
00770
(30K)
Rated fuse voltage [V]
500V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
6
10
15
20
30
40
70
80
90
110
150
175
With power factor
improving reactor
6
10
10
15
25
35
60
70
90
100
125
150
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15
15
15
20
30
40
60
70
90
100
150
175
FR-A840-
00930
(37K)
01160
(45K)
01800
(55K)
02160
(75K)
02600
(90K)
03250
(110K)
03610
(132K)
04320
(160K)
04810
(185K)
05470
(220K)
06100
(250K)
06830
(280K)
Rated fuse voltage [V]
500V or more
Fuse Maximum
allowable rating [A]
*1
Without power
factor improving
reactor
200
250
300
—
—
―
―
―
―
―
―
―
With power factor
improving reactor
175
200
250
300
350
400
500
600
700
800
900
1000
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
225
250
450
450
500
600
800
900
1000
1200
1200
1200
FR-A846-
00023
(0.4K)
00038
(0.75K)
00052
(1.5K)
00083
(2.2K)
00126
(3.7K)
00170
(5.5K)
00250
(7.5K)
00310
(11K)
00380
(15K)
00470
(18.5K)
Rated fuse voltage [V]
500V or more
Fuse Maximum allowable rating [A]
*1
6
10
10
15
25
35
60
70
90
100
Molded case circuit breaker (MCCB)
Maximum allowable rating [A]
*1
15
15
15
20
30
40
60
70
90
100