19
WIRING
3.3
Wiring fundamentals
3.3.1 Cable size
Select the recommended cable size to ensure that a voltage drop will be 2% max.
If the wiring distance is long between the inverter and motor, a main circuit cable voltage drop will cause the motor torque
to decrease especially at the output of a low frequency.
The following tables indicate a selection example for the wiring length of 20m.
200V class, FR-A820 (when input power supply is 220V based on the rated current for 150% overload for 1 minute)
*1
For the FR-A820-03160(55K) or lower the recommended cable size is that of the HIV cable (600V class 2 vinyl-insulated cable) with
continuous maximum permissible temperature of 75°C. Assumes that the surrounding air temperature is 50°C or less and the wiring
distance is 20m or less.
For the FR-A820-03800(75K) or higher the recommended cable size is that of the LMFC cable (heat resistant flexible cross-linked
polyethylene insulated cable) with continuous maximum permissible temperature of 90°C. Assumes that the surrounding air
temperature is 50°C or less and wiring is performed in an enclosure.
*2
The recommended cable size is that of the THHW cable with continuous maximum permissible temperature of 75°C. Assumes that
the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
(Selection example for use mainly in the United States.)
*3
For the FR-A820-00770(15K) or lower the recommended cable size is that of the PVC cable with continuous maximum permissible
temperature of 70°C. Assumes that the surrounding air temperature is 40°C or less and the wiring distance is 20m or less.
For the FR-A820-00930(18.5K) or higher the recommended cable size is that of XLPE cable with continuous maximum permissible
temperature of 90°C. Assumes that the surrounding air temperature is 40°C or less and wiring is performed in an enclosure. (Selection
example for use mainly in Europe.)
*4
The terminal screw size indicates the terminal size for R/L1, S/L2, T/L3, U, V, W, PR, PX, P/+, N/–, P1, P3, and a screw for earthing.
The screw size for PR and PX terminals of FR-A820-00340(5.5K) and FR-A820-00490(7.5K) is indicated in brackets.
The screw size for earthing of FR-A820-00930(18.5K) or higher is indicated in brackets.
Applicable Inverter Type
Terminal Screw Size
*
4
Tightening Torque
[Nm]
Crimping Terminal
R/L1, S/L2, T/L3
U, V, W
FR-A820-00046(0.4K) to
00167(2.2K)
M4
1.5
2-4
2-4
FR-A820-00250(3.7K)
M4
1.5
5.5-4
5.5-4
FR-A820-00340(5.5K)
M5 (M4)
2.5
5.5-5
5.5-5
FR-A820-00490(7.5K)
M5 (M4)
2.5
14-5
8-5
FR-A820-00630(11K)
M5
2.5
14-5
14-5
FR-A820-00770(15K)
M6
4.4
22-6
22-6
FR-A820-00930(18.5K)
M8 (M6)
7.8
38-8
38-8
FR-A820-01250(22K)
M8 (M6)
7.8
38-8
38-8
FR-A820-01540(30K)
M8 (M6)
7.8
60-8
60-8
FR-A820-01870(37K)
M10 (M8)
14.7
80-10
80-10
FR-A820-02330(45K)
M10 (M8)
14.7
100-10
100-10
FR-A820-03160(55K)
M12 (M8)
24.5
100-12
100-12
FR-A820-03800(75K)
M12 (M8)
24.5
150-12
150-12
FR-A820-04750(90K)
M12 (M8)
24.5
150-12
150-12
Applicable Inverter Type
Cable Sizes
HIV, etc. [mm
2
] *
1
AWG/MCM *
2
PVC, etc. [mm
2
] *
3
R/L1,
S/L2,
T/L3
U, V, W
P/+, P1
Earth
Cable
Gauge
R/L1,
S/L2,
T/L3
U, V, W
R/L1,
S/L2,
T/L3
U, V, W
Earth
Cable
Gauge
FR-A820-00046(0.4K) to
00167(2.2K)
2
2
2
2
14
14
2.5
2.5
2.5
FR-A820-00250(3.7K)
3.5
3.5
3.5
3.5
12
12
4
4
4
FR-A820-00340(5.5K)
5.5
5.5
5.5
5.5
10
10
6
6
6
FR-A820-00490(7.5K)
14
8
14
5.5
6
8
16
10
16
FR-A820-00630(11K)
14
14
14
8
6
6
16
16
16
FR-A820-00770(15K)
22
22
22
14
4
4
25
25
16
FR-A820-00930(18.5K)
38
38
38
14
2
2
35
35
25
FR-A820-01250(22K)
38
38
38
22
2
2
35
35
25
FR-A820-01540(30K)
60
60
60
22
1/0
1/0
50
50
25
FR-A820-01870(37K)
80
80
80
22
3/0
3/0
70
70
35
FR-A820-02330(45K)
100
100
100
38
4/0
4/0
95
95
50
FR-A820-03160(55K)
100
100
100
38
4/0
4/0
95
95
50
FR-A820-03800(75K)
125
125
125
38
250
250
—
—
—
FR-A820-04750(90K)
150
150
150
38
300
300
—
—
—