138
Adjustment of analog input
sp
eed limit
(c
alib
ration)
C12
(917)
Terminal 1 bias
frequency (speed)
0.01Hz
0Hz
0 to 400Hz
Set the frequency on the bias side of
terminal 1 input. (valid when
Pr.868
= 5)
{
×
{
C13
(917)
Terminal 1 bias
(speed)
0.1%
0%
0 to 300%
Set the converted % of the bias side
voltage (current) of terminal 1 input. (valid
when
Pr.868
= 5)
{
×
{
C14
(918)
Terminal 1 gain
frequency (speed)
0.01Hz
60Hz
0 to 400Hz
Set the frequency of terminal 1 input gain
(maximum). (valid when
Pr.868
= 5)
{
×
{
C15
(918)
Terminal 1 gain
(speed)
0.1%
100%
0 to 300%
Set the converted % of the gain side
voltage (current) of terminal 1 input. (valid
when
Pr.868
= 5)
{
×
{
Adj
u
st
ment
of
an
alo
g
in
pu
t t
o
rque magn
et
ic f
lux co
mmand
(cal
ibra
tion)
C16
(919)
Terminal 1 bias
command (torque/
magnetic flux)
0.1%
0%
0 to 400%
Set the torque/magnetic flux command
value on the bias side of terminal 1 input.
(valid when
Pr. 868
≠
0, 5)
{
×
{
C17
(919)
Terminal 1 bias
(torque/magnetic
flux)
0.1%
0%
0 to 300%
Set the converted % of the bias side
voltage (current) of terminal 1 input. (valid
when
Pr. 868
≠
0, 5)
{
×
{
C18
(920)
Terminal 1 gain
command (torque/
magnetic flux)
0.1%
150%
0 to 400%
Set the torque/magnetic flux command
value on the gain side of terminal 1 input.
(valid when
Pr. 868
≠
0, 5)
{
×
{
C19
(920)
Terminal 1 gain
(torque/magnetic
flux)
0.1%
100%
0 to 300%
Set the converted % of the gain side
voltage (current) of terminal 1 input. (valid
when
Pr. 868
≠
0, 5)
{
×
{
C38
(932)
Terminal 4 bias
command (torque/
magnetic flux)
0.1%
0%
0 to 400%
Set the torque/magnetic flux command
value on the bias side of terminal 4 input.
(valid when
Pr. 858
=
1, 4)
{
×
{
C39
(932)
Terminal 4 bias
(torque/magnetic
flux)
0.1%
20%
0 to 300%
Set the converted % of the bias side
current (voltage) of terminal 4 input. (valid
when
Pr. 858
= 1, 4)
{
×
{
C40
(933)
Terminal 4 gain
command (torque/
magnetic flux)
0.1%
150%
0 to 400%
Set the torque/magnetic flux command
value on the bias side of terminal 4 input.
(valid when
Pr. 858
=
1, 4)
{
×
{
C41
(933)
Terminal 4 gain
(torque/magnetic
flux)
0.1%
100%
0 to 300%
Set the converted % of the gain side
current (voltage) of terminal 4 input. (valid
when
Pr. 858
= 1, 4)
{
×
{
—
989
Parameter for manufacturer setting. Do not set.
B
u
zzer contr
ol
of the
opera
tion
panel
990
PU buzzer control
1
1
0
Without buzzer
{
{
{
1
With buzzer
PU contrast
a
djustment
991
PU contrast
adjustment
1
58
0 to 63
Contrast adjustment of the LCD of the
parameter unit (FR-PU04/FR-PU07) can
be performed.
0 (Light)
→
63 (Dark)
{
×
{
Para
meter cl
ea
r,
pa
rameter copy
Pr.CL
Parameter clear
1
0
0, 1
Setting "1" returns all parameters except calibration
parameters to the initial values.
ALLC
All parameter clear
1
0
0, 1
Setting "1" returns all parameters to the initial values.
Er.CL
Faults history clear
1
0
0, 1
Setting "1" will clear eight past faults.
PCPY
Parameter copy
1
0
0
Cancel
1
Read the source parameters to the operation panel.
2
Write the parameters copied to the operation panel to the
destination inverter.
3
Verify parameters in the inverter and operation panel.
The parameter number in parentheses is the one for use with the parameter unit (FR-PU04/FR-PU07).
Fu
nc
tio
n
Parameter
Name
Incre
ments
Initial
Value
Range
Description
Para
meter
copy
Param
eter
clear
All
param
eter
clear
Re
la
te
d
p
a
ra
mete
rs
{
: enabled
×
: disabled
Summary of Contents for FR-A741-11K